Text |
| 2013-10-07 14:41:05 | THE CONSTRUCTION APPLICATION SHALL BE ILLUSTRATED IN | | | DETAIL AND CLEARLY INDICATED ON THE PLANS INCLUDING | | | SEPARATION DISTANCES FROM THE HIGH-HAT AND THE DRYWALL. | | | | | | THE SPECIFIED FIRE RATED SILICONE SHALL BE INDICATED ON | | | THE PLAN WITH THE DETAILED APPLICATION INSTRUCTIONS. | | | THE FIRE RATED SILICONE SHALL BE MEET THE | | | REQUIRERMENRTS OF THE PROPOSED CONSTRUCTION | | | APPLICATION. | | | | | | THE LISTING FOR THE HIGH-HAT SHALL SUPPORT (NOT | | | CONFLICT) THE PROPOSED CONSTRUCTION APPLICATION. | | | |
|