| Plan Review Notes For Permit 13090531 |
| Permit Number |
13090531 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-25 15:01:58 | REVIEWED - 9-25-13 | | | | | | 1. WHERE IS PANEL AC1 LOCATED? HOW FAR FROM NEW | | | LOCATION? | | | 2. IS CONDUIT RUN EXPOSED ON ROOF TOP? IF SO, A | | | TEMPEATURE DERATING MAY BE REQUIRED FOR THE CONDUCTORS | | | 3. IF PVC IS USED, EXPANSION FITTINGS ARE REQUIRED | | | 4. HAS VOLTAGE DROP BEEN ADDRESSED? DISTANCE IS | | | INCREASED. | | | VB | | | | | | 10-10-2013 COMMENTS ADDRESS AND ELECTRCIAL APPROVED. | | | REVIEWED BY WDS. |
|