| 2013-09-24 14:15:44 | BUILDING PLAN REVIEW |
| | PERMIT: 13090510 |
| | ADD: 1325 N CONGRESS |
| | CONT: FINANCIAL BUILDING SERVICES |
| | TEL: (954)444-0785 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SEPT 24/ 2013 |
| | ACTION: PROVISO |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) PLEASE SUBMIT MULLION PRODUCT APPROVAL. 2010 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS |
| | & CLADDING.FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31)(B) MULLIONS. |
| | |
| | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) 1714.5.5.2 LOAD TRANSFER. MULLIONS SHALL BE DESIGNED |
| | TO TRANSFER THE DESIGN PRESSURE LOADS APPLIED BY THE |
| | WINDOW AND DOOR ASSEMBLIES TO THE ROUGH OPENING |
| | SUBSTRATE. 1714.5.5.4 STRUCTURAL SAFETY FACTOR. |
| | MULLIONS SHALL BE CAPABLE OF RESISTING A LOAD OF |
| | ONE-AND-ONE-HALF TIMES THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW AND DOOR ASSEMBLIES TO BE |
| | SUPPORTED WITHOUT EXCEEDING THE APPROPRIATE MATERIAL |
| | STRESS LEVELS. IF TESTED BY AN APPROVED LABORATORY, THE |
| | ONE AND ONE-HALF TIMES THE DESIGN PRESSURE LOAD SHALL |
| | BE SUSTAINED FOR 10 SECONDS, AND THE PERMANENT |
| | DEFORMATION SHALL NOT EXCEED 0.4 PERCENT OF THE MULLION |
| | SPAN AFTER THE ONE-AND-ONE-HALF TIMES DESIGN PRESSURE |
| | LOAD IS REMOVED. |
| | |