| 2014-01-03 13:53:50 | REVISION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | ***NOTE: |
| | REVISIONS TO EXTERIOR OF BUILDING NEED TO BE APPROVED |
| | BY HISTORIC. |
| | |
| | |
| | 1- PLANS SUBMITTED ARE DIFFERENT FROM THE ONES THAT |
| | WERE APPROVED. PROVIDE COMPLETE FRAMING DETAILS AND |
| | SPECIFICATIONS FOR THE CLOSING OF EXISTING EXTERIOR |
| | OPENINGS TO SHOW COMPLIANCE WITH SEC. R301 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 2- PLANS SHOW REMOVING PORTION OF EXISTING STAIRWAY |
| | WALLS TO ALLOW FOR NEW IRON HAND-RAILINGS. AND NEW |
| | OPENING FOR HALF BATHROOM ENTRANCE. THESE WALLS SEEM TO |
| | BE BEARING WALLS. PROVIDE COMPLETE ENGINEERING |
| | ANALYSIS, DETAILS AND SPECIFICATIONS TO SHOW THAT |
| | STRUCTURE IS GOING TO BE STRUCTURALLY SOUND. SEC. R301 |
| | OF 2010 FBC AND SEC. 107.2.1.3 OF CITY AMENDMENTS TO |
| | FBC. |
| | |
| | 3- PROVIDE COMPLETE CONSTRUCTION DETAILS AND |
| | SPECIFICATIONS FOR THE NEW HANDRAIL/GUARDRAIL TO SHOW |
| | COMPLIANCE WITH SEC. R311.7.7 AND THE LIVE LOADS AS |
| | REQUIRED BY TABLE R301.5 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 4- PROVIDE DIMENSIONS FOR ALTERATIONS ON BEDROOM #3 TO |
| | SHOW COMPLIANCE WITH SEC. R304 OF 2010 FBC-RESIDENTIAL. |
| | |
| | |
| | ***NOTE: NEED A/C AND PLUMBING PERMITS. |
| | |
| | |
| | ****REMAINDER: THE FOLLOWING INFORMATION REQUESTED ON |
| | PROVISO NEED TO BE PROVIDED. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL FOR EXTERIOR DOORS (AS |
| | REQUESTED ON PROVISO. (SEE APPROVED PLANS). |
| | |