| 2013-10-31 17:18:00 | THE ELECTRICAL PORTION OF THIS PERMIT WAS APPROVED WITH | | | THE FOLLOWING NOTATIONS & CONDITIONS: | | | 1. THE NEC LIMITS THE NUMBER OF PERMISSIBLE BENDS FOR A | | | CONTINUOUS UNINTERRUPTED RACEWAY. THIS REQUIREMENTS | | | CONFLICTS AND THUS SUPERSEDES THE DESIGN NOTES 5 & 11 | | | ON PAGE E111; NOTE 12 OF P[AGE E112. | | | 2. BECAUSE THE SUBMITTED PLANS FAIL TO PROVIDE ACCURATE | | | DETAILS FOR THE ELECTRICAL RISER, AN "AS BUILT" | | | REVISION TO THE RISER SHALL BE SUBMITTED FOR REVIEW AND | | | APPROVAL BEFORE FINAL INSPECTION. |
|