Plan Review Notes
Plan Review Notes For Permit 13090417
Permit Number 13090417
Review Stop B
Sequence Number 2
Notes
Date Text
2013-10-30 10:15:08BUILDING PLAN REVIEW
 PERMIT:13090417
 ADD: 1751 PALM BEACH LAKES SUITE E111
 CONT: TBD
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: WED OCT. 30/ 2013
 ACTION: BUILDING PROVISO
  
 1) PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 2) BUILDING PROVISO:
 SHEET A1.2 DETAIL # 2 MICROWAVE, THE BOTTOM OF THE
 SHELF IS 44 INCHES FROM FINISH FLOOR.
 2010 FL ACCESS CODE, 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308.
 308.2.2 OBSTRUCTED HIGH REACH.
 WHERE A HIGH FORWARD REACH IS OVER AN OBSTRUCTION, THE
 CLEAR FLOOR SPACE SHALL EXTEND BENEATH THE ELEMENT FOR
 A DISTANCE NOT LESS THAN THE REQUIRED REACH DEPTH OVER
 THE OBSTRUCTION. THE HIGH FORWARD REACH SHALL BE 48
 INCHES (1220 MM) MAXIMUM WHERE THE REACH DEPTH IS 20
 INCHES (510 MM) MAXIMUM. WHERE THE REACH DEPTH EXCEEDS
 20 INCHES (510 MM), THE HIGH FORWARD REACH SHALL BE 44
 INCHES (1120 MM) MAXIMUM AND THE REACH DEPTH SHALL BE
 25 INCHES (635 MM) MAXIMUM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  