| Date |
Text |
| 2013-09-19 15:22:23 | PERMIT #13090417 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | FAIL COMMENT: PER NFPA 101, SECTION 36.2.5.11 EXIT |
| | ACCESS IN CLASS A AND CLASS B MERCANTILE OCCUPANCIES |
| | THAT ARE PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH 9.7.1.1(1), AND EXIT ACCESS IN ALL CLASS C |
| | MERCANTILE OCCUPANCIES, SHALL BE PERMITTED TO PASS |
| | THROUGH STOREROOMS, PROVIDED THAT ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1)NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE |
| | PROVIDED THROUGH THE STOREROOM. |
| | (2)THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING. |
| | (3)THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT |
| | LESS THAN 44 IN. (1120 MM) WIDE. |
| | (4)THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE |
| | DEFINED, DIRECT, AND CONTINUOUSLY MAINTAINED IN AN |
| | UNOBSTRUCTED CONDITION. |
| | |
| | THE SPEAKER SYSTEM WILL NEED TO BE TESTED AGAINST THE |
| | FIRE ALARM SYSTEM TO ENSURE THAT THE MINIMUM REQUIRED |
| | DECIBAL LEVELS OF THE FIRE ALARM SYSTEM ARE BEING MET. |
| | PENDING RESULTS OF FIELD INSPECTION/FIRE ALARM TEST, |
| | ADDITIONAL REQUIREMENTS MAY BE NEEDED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) |
| | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND |
| | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| | 500 NORTH DIXIE HIGHWAY. |
| | |
| | ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A |
| | LOCK/UNLOCK INDICATOR. |
| | |
| | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH |
| | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL |
| | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| | SPACED NOT MORE THAN 15 FEET ON CENTER. |
| | |
| | AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY |
| | EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL |
| | EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED |
| | WITH RESPECT TO THEIR DUTIES UNDER THE PLAN. |
| | |
| | EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED |
| | IN THE USE OF PORTABLE FIRE EXTINGUISHERS. |
| | |
| | SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE |
| | FIRE ALARM AND SPRINKLER SYSTEM. |
| | |
| | SUE ELLEN CALDERON |
| | FIRE INSPECTOR & INVESTIGATOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 804-4751 |
| | |
| | |
| | |