| 2013-09-18 07:06:48 | BUILDING PLAN REVIEW |
| | PERMIT:13090417 |
| | ADD: 1751 PALM BEACH LAKES SUITE E111 |
| | CONT: TBD |
| | TEL: (561)373-3902 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED SEPT 18/ 2013 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) PB OUTLET MALLS: |
| | BUILDING PROVISO: |
| | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL |
| | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT |
| | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT |
| | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | |
| | 2) BUILDING PROVISO: |
| | SHEET A1.0 BACK EXIT WILL REQUIRE COMPLIANCE WITH: 2010 |
| | FBC 1014.2.4 EXCEPTION # 2, EGRESS THROUGH INTERVENING |
| | SPACES: |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE |
| | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA |
| | TO THE EXIT WITHOUT OBSTRUCTIONS. |
| | |
| | 3) BUILDING PROVISO: |
| | SHEET A1.2 DETAIL # 2 MICROWAVE, THE BOTTOM OF THE |
| | SHELF IS 54 INCHES FROM FINISH FLOOR. |
| | 2010 FL ACCESS CODE, 309.3 HEIGHT. OPERABLE PARTS SHALL |
| | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. |
| | 308.2.2 OBSTRUCTED HIGH REACH. |
| | WHERE A HIGH FORWARD REACH IS OVER AN OBSTRUCTION, THE |
| | CLEAR FLOOR SPACE SHALL EXTEND BENEATH THE ELEMENT FOR |
| | A DISTANCE NOT LESS THAN THE REQUIRED REACH DEPTH OVER |
| | THE OBSTRUCTION. THE HIGH FORWARD REACH SHALL BE 48 |
| | INCHES (1220 MM) MAXIMUM WHERE THE REACH DEPTH IS 20 |
| | INCHES (510 MM) MAXIMUM. WHERE THE REACH DEPTH EXCEEDS |
| | 20 INCHES (510 MM), THE HIGH FORWARD REACH SHALL BE 44 |
| | INCHES (1120 MM) MAXIMUM AND THE REACH DEPTH SHALL BE |
| | 25 INCHES (635 MM) MAXIMUM. |
| | |
| | 4) BUILDING PROVISO: |
| | SHEET A8.0 DETAIL # 3. ACCESSIBLE BENCH IS MISSING |
| | BACK. |
| | 903.4 BACK SUPPORT. |
| | THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE |
| | AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES |
| | (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2 |
| | INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A |
| | POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT |
| | SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM) |
| | MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED |
| | HORIZONTALLY. |
| | ADVISORY 903.4 BACK SUPPORT. |
| | TO ASSIST IN TRANSFERRING TO THE BENCH, CONSIDER |
| | PROVIDING GRAB BARS ON A WALL ADJACENT TO THE BENCH, |
| | BUT NOT ON THE SEAT BACK. IF PROVIDED, GRAB BARS CANNOT |
| | OBSTRUCT TRANSFER TO THE BENCH. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |