| Plan Review Notes For Permit 13090405 |
| Permit Number |
13090405 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-10-22 09:55:37 | BUILDING PROVISO | | | | | | 1) SUBMIT TWO COPIES OF THE ICC EVALUATION REPORT FOR | | | THE ICYNENE SPRAY FOAM INSULATION THAT WILL BE | | | INSTALLED. FBC R316 | | | | | | 2) THE RAS 117 CALCULATIONS FOR THE FLAT ROOF BASE | | | SHEET FASTENING FROM DANIEL J. MOSS, P.E. DO NOT HAVE | | | HIS HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT | | | ACCEPTABLE) AS REQUIRED BY FAC 61G15-23.002. SUBMIT RAS | | | 117 CALCULATIONS WITH ORIGINAL SIGNATURES. ALSO THE | | | ADDRESS FOR THE CITY OF WEST PALM BEACH IS INCORRECT ON | | | THE DOCUMENT. PLEASE CORRECT THE ADDRESS TO 401 | | | CLEMATIS STREET WEST PALM BEACH FL 33401. | | | | | | 3) THE ENERGY CALCULATIONS THAT WERE SUBMITTED STILL | | | APPEAR TO BE IN ERROR. A 2 FT. OVERHANG IS STILL LISTED | | | AND THE STRUCTURE HAS NO OVERHANG. ALSO THE GLAZED AREA | | | AT THE NORTH ELEVATION DOES NOT APPEAR TO INCLUDE THE | | | TOTAL AREA OF THE (2) 5' X 8' GLAZED FRENCH DOORS AND | | | THE SPECIFIED AREAS ARE UNCLEAR. PLEASE SUBMIT TWO | | | REVISED SIGNED SETS. 2010 FBC ENERGY CONSERVATION | | | SECTIONS 405.5.1, 405.5.2 AND 405.5.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|