2013-10-22 09:55:37BUILDING PROVISO
  
 1) SUBMIT TWO COPIES OF THE ICC EVALUATION REPORT FOR
 THE ICYNENE SPRAY FOAM INSULATION THAT WILL BE
 INSTALLED. FBC R316
  
 2) THE RAS 117 CALCULATIONS FOR THE FLAT ROOF BASE
 SHEET FASTENING FROM DANIEL J. MOSS, P.E. DO NOT HAVE
 HIS HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT
 ACCEPTABLE) AS REQUIRED BY FAC 61G15-23.002. SUBMIT RAS
 117 CALCULATIONS WITH ORIGINAL SIGNATURES. ALSO THE
 ADDRESS FOR THE CITY OF WEST PALM BEACH IS INCORRECT ON
 THE DOCUMENT. PLEASE CORRECT THE ADDRESS TO 401
 CLEMATIS STREET WEST PALM BEACH FL 33401.
  
 3) THE ENERGY CALCULATIONS THAT WERE SUBMITTED STILL
 APPEAR TO BE IN ERROR. A 2 FT. OVERHANG IS STILL LISTED
 AND THE STRUCTURE HAS NO OVERHANG. ALSO THE GLAZED AREA
 AT THE NORTH ELEVATION DOES NOT APPEAR TO INCLUDE THE
 TOTAL AREA OF THE (2) 5' X 8' GLAZED FRENCH DOORS AND
 THE SPECIFIED AREAS ARE UNCLEAR. PLEASE SUBMIT TWO
 REVISED SIGNED SETS. 2010 FBC ENERGY CONSERVATION
 SECTIONS 405.5.1, 405.5.2 AND 405.5.3
  