Plan Review Notes
Plan Review Notes For Permit 13090405
Permit Number 13090405
Review Stop M
Sequence Number 1
Notes
Date Text
2013-09-27 10:46:332010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF MECHANICAL PLANS THAT SHOW THE
 LOCATION OF THE EQUIPMENT AND THE DUCT SYSTEM. SPECIFY
 THE SUPPLY / RETURN DUCT AND GRILL LOCATIONS AND SIZES.
 INDICATE THE CFMS AT EACH SUPPLY OUTLET. FBCR M1601.1
 AND CITY AMENDMENTS 107.3.5
  
 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN
 THAT CORRESPONDS WITH THE EQUIPMENT SIZING
 CALCULATIONS. FBCR M1401.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]