| Plan Review Notes For Permit 13090405 |
| Permit Number |
13090405 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-27 11:26:00 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENERGY CALCULATIONS CONTAIN SEVERAL ERRORS. | | | ENERGY CALCULATIONS ARE REQUIRED TO BE SPECIFIC TO THE | | | ORIENTATION OF THE BUILDING. WORST CASE CAN NOT BE | | | USED. THE FORM USES AN OVERHANG OF 2 FEET WHEN THERE | | | ISN'T ANY. A 50 GAL. WATER HEATER IS SPECIFIED ON THE | | | FORM AND THE PLANS SHOW A 30 GALLON. THE OWNER/AGENT IS | | | REQUIRED TO SIGN THE ENERGY FORMS. 2010 FBC ENERGY | | | CONSERVATION SECTION 405. | | | | | | 2) SHOW COMPLIANCE WITH FBC 318.6 WHICH REQUIRES | | | GUTTERS WITH DOWNSPOUTS THAT DISCHARGE ONE FOOT AWAY | | | FROM THE STRUCTURE WALLS FOR BUILDINGS WITH LESS THAN 6 | | | INCHES OF HORIZONTAL EAVE PROJECTION. | | | | | | 3) SHOW COMPLIANCE WITH FBC 806.1 FOR ATTIC / ROOF | | | VENTILATION. | | | | | | 4) SPECIFY THE FASTENING OPTION AND MAXIMUM DESIGN | | | PRESSURE FOR THE ASSEMBLY ON PAGE 29 OF THE GAF | | | RUBEROID PRODUCT APPROVAL (NOA NO. 09-0224.01) THAT | | | WILL BE USED. SUBMIT TWO COPIES OF SIGNED AND SEALED | | | RAS 117 CALCULATIONS FOR ENHANCED FASTENING AT | | | PERIMETER AND CORNER AREAS IN COMPLIANCE WITH | | | LIMITATION NUMBER 7 OF THE NOA. FBC R301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|