| 2013-10-26 14:29:38 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |
| | COMMENTS FROM PREVIOUS LISTS NOT ADDRESSED. NO TEST |
| | REPORTS SUBMITTED, VALUE ISSUE NOT ADDRESSED. |
| | |
| | SPEC SHEET SHOWING STC AND ICC DATA FROM MANUFACTURER |
| | IS ***NOT*** THE SAME AS A COPY OF THE TEST. FLAME |
| | SPREAD INFORMATION/TEST NOT PROVIDED. |
| | |
| | PLEASE DO NOT RESUBMIT WITHOUT SPEAKING WITH ME UNLESS |
| | YOU UNDERSTAND THE COMMENTS. OR, HAVE THE |
| | MANUFACTURER'S TECHNICAL REPRESENTATIVE CONTACT ME. |
| | |
| | FBC FLORIDA BUILDING CODE 2010 |
| | |
| | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| | NOT BE ALTERED. |
| | |
| | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| | BELOW WILL NOT BE ALTERED. |
| | |
| | 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E 84 OR UL 723. |
| | |
| | 4. VALUE TO INCLUDE LABOR AND MATERIALS FBC 107. |
| | PROVIDE A PLAN WHICH SHOWS AREAS TO HAVE NEW TILE |
| | INSTALLED, WITH SQUARE FOOT AREAS. |
| | |