| Plan Review Notes For Permit 13090363 |
| Permit Number |
13090363 |
|
| Review Stop |
Z |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-06-12 14:09:55 | FAILED | | | | | | PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS. | | | | | | 1) REPEAT COMMENT: PROVIDE THE REVISED EAST FACADE | | | ELEVATION WITH GLAZING CALCULATIONS WHICH VERIFY THAT | | | THE REPLACEMENT WINDOWS CONTINUE TO MEET THE GLAZING | | | REQUIREMENTS OF THE NORTHWOOD MIXED USE DISTRICT. | | | PLEASE REMEMBER THE AMOUNT OF GLAZING SHALL BE SHOWN | | | BETWEEN TWO (2) AND EIGHT (8) FEET FOR ALL THE WINDOWS | | | ON THE EASTERN FACADE. | | | | | | 2) NO INFORMATION WAS PROVIDED FOR EITHER GROUP OF THE | | | PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH THE | | | FOLLOWING PROVISIONS OF THE NORTHWOOD MIXED USE | | | DISTRICT. | | | | | | A. WINDOWS SHALL BE RECESSED A MINIMUM OF TWO INCHES | | | FROM THE EXTERIOR FACE OF THE FACADE. | | | | | | B. MULTIPLE WINDOWS IN THE SAME ROUGH OPENING SHALL BE | | | SEPARATED BY A FOUR-INCH WIDE POST AND SIT ON ONE | | | CONTINUOUS SILL. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | 2014-05-21 15:35:57 | 5/21/14 SENT TO ES. |
|