| 2013-10-02 07:18:48 | PROVIDE DETAILS OF SIGNS AND LETTERS, INCLUDING | | | LOCATIONS AND NUMBER OF ATTACHMENTS FOR EACH LETTER. | | | PROVIDE DETAILS OF SIGN CONSTRUCTION AND CLEARLY | | | INDICATE LOAD PATH | | | PROVIDE DIMENSIONS OF LETTERS LOCATED FROM THE WALL SO | | | WINLOADS CAN BE EVALUATED | | | HOW CAN EPOXY SET ROD BE USED IN HOLLOW CONCRETE AS | | | INDICATED ON THE DRAWINGS? | | | DESIGN APPEARS TO BE FOR A BOX SIGN AND APPLCIATION | | | INDICATES ILLUMINATED LETTERS. | | | PROVIDE DETAILS OF LOADS AND NUMBER OF DRIVERS WITH | | | SPECIFIC LOADS TO THE DRIVER | | | PROVIDE REQUIRED ELECTRICAL CIRCUIT INFORMATION | | | PROVIDE PHOTOCELL AND/OR TIMECLOCK WITH PROGRAMMING | | | BACKUP PER FBC-EC 505.2 | | | PROVIDE UL CERTIFICATION PER NEC 600 AND ALL DETAILS | | | PER NEC AND ENERGY CODE | | | INSUFFICIENT INFORMATION PROVIDED FOR REVIEW |
|