| Plan Review Notes For Permit 13090329 |
| Permit Number |
13090329 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-04-17 10:43:50 | 1) SHT. A-6 - THE CLEAR FLOOR SPACE FOR THE DRINKING | | | FOUNTAIN DOES NOT COMPLY WITH THE 2010 FL. | | | ACCESSIBILITY CODE SEC.602. THE CLEAR FLOOR SPACE SHALL | | | BE CENTERED ON THE UNIT. THE PLANS SHOW THE CLEAR FLOOR | | | SPACE CENTERED ON BOTH DRINKING FOUNTAINS AS A WHOLE. | | | THE CLEAR FLOOR SPACE SHALL BE CENTERED ON THE LOW UNIT | | | PER THIS CODE SECTION.AS DESIGNED THERE IS NOT 15 | | | INCHES TO THE CENTER OF THE LOW UNIT. | | | 2) THE VENT FOR THE FLOOR DRAIN IN THE MEZZANINE SHALL | | | CONNECT TO THE HORIZONTAL DRAIN ABOVE THE CENTERLINE OF | | | THE HORIZONTAL DRAIN PIPE. AS DRAWN, IT IS A FLAT, DRY | | | VENT WHICH IS PROHIBITED BY THE PLUMBING CODE.SEC. | | | 905.3. | | | | | | PLEASE CONTACT ME SO WE CAN DISCUSS THESE ITEMS TO GET | | | THEM RECTIFIED SO I CAN APPROVE THE PLUMBING PORTION OF | | | THE REVIEW. THANK YOU. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|