2015-04-17 10:43:501) SHT. A-6 - THE CLEAR FLOOR SPACE FOR THE DRINKING
 FOUNTAIN DOES NOT COMPLY WITH THE 2010 FL.
 ACCESSIBILITY CODE SEC.602. THE CLEAR FLOOR SPACE SHALL
 BE CENTERED ON THE UNIT. THE PLANS SHOW THE CLEAR FLOOR
 SPACE CENTERED ON BOTH DRINKING FOUNTAINS AS A WHOLE.
 THE CLEAR FLOOR SPACE SHALL BE CENTERED ON THE LOW UNIT
 PER THIS CODE SECTION.AS DESIGNED THERE IS NOT 15
 INCHES TO THE CENTER OF THE LOW UNIT.
 2) THE VENT FOR THE FLOOR DRAIN IN THE MEZZANINE SHALL
 CONNECT TO THE HORIZONTAL DRAIN ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. AS DRAWN, IT IS A FLAT, DRY
 VENT WHICH IS PROHIBITED BY THE PLUMBING CODE.SEC.
 905.3.
  
 PLEASE CONTACT ME SO WE CAN DISCUSS THESE ITEMS TO GET
 THEM RECTIFIED SO I CAN APPROVE THE PLUMBING PORTION OF
 THE REVIEW. THANK YOU.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  