| 2015-05-14 12:22:54 | REVIEW BY CHRIS COLE | | | | | | 1) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN AND SUBMIT | | | SPECS FOR THE EXHAUST FAN AT THE DUMPSTER ENCLOSURE. | | | 2) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE | | | RTU CURBS, THE REFRIGERATION CONDENSER STAND, AND THE | | | ROOF TOP EXHAUST AND SUPPLY FANS. | | | INCLUDE THE UNIT ATTACHMENT DETAILS TO THE CURBS AND | | | STANDS, AND SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE | | | NOA FOR THE CONDENSER STAND. | | | 3) PURSUANT TO PLANNING AND ZONING COMMENTS, AND | | | SECTION 304.11 FMC-2010, PROVIDE EITHER A 42" HIGH | | | PARAPET OR GUARD AT ANY ROOF EDGES WITHIN 10' OF THE | | | HVAC EQUIPMENT. | | | 4) PLACE NOTES ON THE PLAN INDICATING SEPARATE PERMITS | | | WILL BE OBTAINED FOR THE KITCHEN HOODS, AND FOR THE | | | REFRIGERATION. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|