| 2015-03-31 15:40:26 | BUILDING PLAN REVIEW |
| | PERMIT: 13090329 |
| | ADD: 5011 BROADWAY |
| | CONT: TO BE DETERMINED |
| | TEL: (305)331-1400 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: TUES. MARCH 30/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| | STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF |
| | FOUR TIMES THE FEE FOR |
| | PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES |
| | FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) SHEET A-1: COMPLIED> |
| | , |
| | 1B) 4TH REQUEST: SHEET A1 BUILDING DESIGN.THE RESPONSE |
| | COMMENTS STATE THE PLANS WERE UPDATED TO A 5-B W/ |
| | SPRINKLERS, REQUIRING NO FIRE RATING. REVISED DATE |
| | 3/16/15 STILL SHOWS THE BUILDING AS A TYPE III-B FIRE |
| | SPRINKLERED, PROTECTED. |
| | |
| | THE MINIMUM BUILDING TYPE OF CONSTRUCTION |
| | 107.3.5.1.1(3) TABLE 503. |
| | SHEET A1 INDICATES THIS BUILDING IS DESIGNED AS A TYPE |
| | III-B FIRE SPRINKLERED PROTECTED (1 HOUR FIRE RATING). |
| | SEE 2007 CODE COMMENTARY FBC-B TABLE 601 OFTEN TYPE A |
| | OR B ARE REFEFFED TO AS PROTECTED AND UNPROTECTED |
| | CONSTRUCTION, RESPECTIVELY. PLEASE NOTE THIS |
| | TERMINOLOGY DOES NOT REFER TO WHETHER THE BUILDING IS |
| | SPRINKLERED OR NOT. |
| | THE A REFERS TO REQUIRED FIRE RATINGS FOR EXTERIOR |
| | WALLS PRIMARY STRUCTURAL FRAME, ROOF CONSTRUCTION AND |
| | SECONDARY MEMBERS. 2010 FBC-B TABLE 601 FOOTNOTE B |
| | PROVIDES REDUCTION IN HOURS, A TYPE BUILDING ALL |
| | REQUIRE A MINIMUM OF 1 HOUR FIRE RATING OF ROOF FRAMING |
| | MEMBERS, SEE BUILDING TYPE IIIA FOOTNOTES ,B, C &D. |
| | SHEET A8 THE STRUCTURAL ELEMENTS DOES NOT INDICATE ANY |
| | RATING ON STRUCTURAL MEMBERS. |
| | |
| | 1C) 4TH REQUEST. THE RESPONSE LETTER INDICATES FIRE |
| | SPRINKLER SHOP DRAWINGS ARE ATTACHED. NOTE NO FIRE |
| | SPRINKLER PLANS ARE ATTACHED. THERE ARE (2) SETS OF |
| | FIRE ALAARM PLANS FOLDED NOT PART OF THE SUBMITTAL SET. |
| | WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | STANDPIPES |
| | PRE-ENGINEERED SYSTEMS |
| | FIRE PROTECTION NOTES INDICATE THAT THE BUILDING IS TO |
| | BE FIRE SPRINKLERED, THE 2010 FBC-B 903.2.7 NEW WORK |
| | REQUIRES SPRINKLERS FOR MERCANTILE AREAS WITH A FIRE |
| | AREA GREATER THAN 12,000 SQ FT. NO FIRE SPRINKLER PLANS |
| | WERE SUBMITTED. 107.3.5.1.1( 5) FIRE SUPPRESSION. NOTES |
| | ON THE PLAN DO NOT CONSTITUTE COMPLIANCE WITH THIS |
| | SECTION. THERE HAS TO BE A DESIGN CRITERIA FOR THE |
| | SIZING OF THE UNDER GROUND FIRE MAIN THAT WILL BE |
| | REQUIRED TO COME INTO THIS BUILDING. NO SIZING HAS BEEN |
| | SUBMITTED. |
| | |
| | 1D) PROVISO: |
| | ROOFING ON THE MAIN ROOF WAS COMPLETED A FEW YEARS AGO. |
| | ROOFING CONTRACTOR WILL BE NEEDED FOR ROOF FLASHING OF |
| | NEW A/C CURBS, STANDS, ROOF HATCH AND ANY FLASHING WORK |
| | AT PARAPET WALL. ROOFING CONTRACTOR TO SUBMIT A |
| | SEPARATE ROOFING PRODUCT APPROVAL FOR TIE IN OF THE |
| | EXISSTING ROOF. |
| | |
| | |
| | 2-4) COMPLIED. |
| | |
| | 5) PROVISO: NEW COOLERS AND FREZZERS ARE UNDER SEPARATE |
| | PERMIT. NOT PART OF THIS REVIEW. |
| | |
| | 6) PROVISO: AWNINGS ARE UNDER A SEPARATE PERMIT, NOT |
| | PART OF THIS REVIEW AS WELL AS SIGNS. |
| | |
| | 7-12 COMPLIED. |
| | |