2014-10-27 13:10:26WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) SHT. A-6 - THE ELEVATION DETAILS ON THE PLAN ARE
 NOTED AS BEING ON SHT. A-5. REVISE ALL THE DETAILS TO
 SHOW SHT. A-6 WHICH IS THE PAGE WHERE THEY ARE LOCATED.
 2) NONE OF THE ELEVATIONS ON SHT. A-6 CORRELATE WITH
 THE FLOOR PLAN.
 3) THE FLUSH VALVE ON THE WATER CLOSET IN THE WOMEN'S
 RESTROOM SHALL BE ON THE WIDE SIDE OF THE WATER CLOSET
 PER THE 2010 FBC, ACCESSIBILITY, SEC. 604.6.
 4) THE TOILET PAPER DISPENSER SHALL BE LOCATED A
 MINIMUM OF 7" AND A MAXIMUM OF 9" IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
 5) SHOW THE DIMENSIONS OF THE REQUIRED CLEAR FLOOR
 SPACE FOR THE LAVATORY AND THE WATER CLOSET IN THE
 TOILET ROOMS. COMPLY WITH SECS. 305.3 AND 604.3.1.
 6) SHT. A-6 - ELEVATION 9/A-5 - THIS ELEVATION DOESN'T
 CORRELATE WITH ANY OF THE TOILET ROOMS. DELETE THIS
 ELEVATION.
 7) SHT. A-6- ELEVATION "C" - SHOW THE HEIGHT OF THE
 SPOUT ON THE DRINKING FOUNTAIN FOR STANDING PERSONS PER
 THE 2010 FL. ACCESSIBILITY CODE SEC. 602.7.
 8) SHT. A-6 - KNEE AND TOE CLEARANCES FOR THE
 ACCESSIBLE DRINKING FOUNTAIN SHALL BE A MIN. OF 30
 INCHES WIDE PER THE 2010 FAC SECS. 305.3, 306.2.5,
 306.3.5. THE CLEAR FLOOR SPACE SHALL BE CENTERED ON THE
 UNIT. AS DESIGNED, THE DRINKING FOUNTAINS DO NOT COMPLY
 WITH THESE CODE SECTIONS.
 9) THE VENT FOR THE DUMPSTER SHALL COMPLY WITH THE 2010
 FLORIDA PLUMBING CODE SEC.905.3. A FLAT, DRY VENT IS
 NOT PERMITTED.
 10) THE DISCHARGE FROM THE REFRIGERATED CASES SHALL NOT
 DISCHARGE TO THE GREASY WASTE SYSTEM PER THE 2010 FPC
 SEC.1003.2.
 11) ANY INDIRECT WASTE THAT EXCEEDS 2 FT. IN LENGTH
 HORIZONTALLY OR 4 FT. IN TOTAL DEVELOPED LENGTH SHALL
 BE TRAPPED PER THE 2010 FBC SEC.802.2.
 12) SUBMIT CALCULATIONS FOR THE GREASE TRAP IN
 ACCORDANCE WITH SEC. 1003.5.1.
 13) SHT. P-1 - REFERS TO DETAIL 3/P-1 FOR FRENCH DRAIN
 DETAIL.THERE IS NO SUCH DETAIL ON THE PLAN.
 14) THE FLOOR DRAIN IN THE THE MEZZANINE EXCEEDS THE
 DISTANCE FROM A VENT PER TABLE 906.1. 2010 FPC .
 15) LABEL THE MOP SINK AS SUCH ON THE SANITARY RISER.
 16) SHT. P-2- SHOW ALL THE INDIRECT WASTES TO THE FLOOR
 DRAINS ON SHT. P-2.
 17) SHT. P-4 - ALL HOSE BIBBS SHALL BE EQUIPPED WITH
 SHUTOFF VALVES PER SEC. 606.2 (2) OF 2010 FPC.
 18) SUBMIT INFO ON THE TRAP PRIMER VALVES FOR THE FLOOR
 DRAINS. THE WATER RISER SHOWS SHUTOFF VALVES ON THE
 TRAP PRIMER LINES. 1002.4.TRAP SEAL PRIMER VALVES SHALL
 COMPLY W/ ASSE 1018 OR ASSE 1044.
 19) THE TRAP SEAL LINE FOR THE FLOOR DRAIN BY ESPRESSO
 MACHINE IS NOT SHOWN ON THE WATER RISER.
 20) SUBMIT SPECIFICATIONS FOR THE WATER HEATER.SHOW THE
 SIZE OF THE PAN AND PAN DRAIN ON THE DETAIL. THE PAN
 AND DRAIN SHALL COMPLY W/ SEC. 504.7.1
 21) A MEANS OF CONTROLLING INCREASED PRESSURE DUE TO
 THERMAL EXPANSION SHALL BE PROVIDED PER 2010 FPC
 SEC.607.3
 22) THE HOT WATER RECIRCULATING LINE SHALL COMPLY W/
 2010 FPC SEC.607.2 & SEC. 504.6 OF THE FL. ENERGY CODE.
  