2014-10-27 11:45:261) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT / APPLIANCES. EQUIPMENT / APPLIANCES SHALL BE
 LISTED AND LABELED PER THE 2010 FL. GAS CODE SEC.
 301.3.
 2) THE GAS PIPING IS UNDERSIZED FOR THE TOTAL LOAD
 CONNECTED THERETO. THE MAXIMUM LOAD FOR A 1" LINE AT 50
 FT. WITH 552,000 BTU LOAD IS 480,000 BTU'S. THE MINIMUM
 SIZE SHALL BE 1 1/4" PER TABLE 402.4 (26 ) OF THE 2010
 FGC.
 3) THE SEDIMENT TRAPS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE 2010 FGC SEC.408.4.408.4 SEDIMENT TRAP.
 WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE , A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT
 TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED
 NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE
 BOTTOMMOST OPENING OF THE TEE OR OTHER DEVICE APPROVED
 AS AN EFFECTIVE SEDIMENT TRAP. ILLUMINATING APPLIANCES,
 RANGES, CLOTHES DRYERS AND OUTDOOR GRILLS NEED NOT BE
 SO EQUIPPED.
 4) SUBMIT DETAILS FOR THE ANCHORING OF THE LP TANKS.
 TANKS SHALL BE ANCHORED TO WITHSTAND THE WIND LOADS PER
 THE 2010 FBC SEC.1609.
 5) THE LOCATION OF THE LP TANKS IN RELATION TO BUILDING
 OPENINGS LOCATED BELOW THE RELIEF VALVE OF THE TANKS
 AND THE DISTANCE AWAY FROM ANY SOURCE OF IGNITION SHALL
 COMPLY W/NFPA 58, SEC.6.3.7 (1) AND (2). SHOW THE
 DISTANCE OGF THE LP TANKS FROM THE DOOR AND ANY SOURCE
 OF IGNITION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
2014-10-15 11:39:47NEW SHEET P-4 SUBMITTED. JG.