| 2014-11-10 11:09:10 | BUILDING PLAN REVIEW |
| | PERMIT: 13090329 |
| | ADD: 5011 BROADWAY |
| | CONT: TO BE DETERMINED |
| | TEL: (305)331-1400 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. NOV. 11/ 2014 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| | STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF |
| | FOUR TIMES THE FEE FOR |
| | PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES |
| | FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) SHEET A-1: |
| | 1A) COMPLIED> |
| | MISSING TO WHAT EDITION OF CODE THIS BUILDING DESIGN |
| | AND PERMIT WERE DESIGNED TO, 2010 FBC-B, 2010 FL |
| | EXISTING BUILDING CODE & 2010 FL ACCESSIBILITY CODE, |
| | 1B) 3RD REQUEST: |
| | THE MINIMUM BUILDING TYPE OF CONSTRUCTION |
| | 107.3.5.1.1(3) TABLE 503. |
| | SHEET A1 INDICATES THIS BUILDING IS DESIGNED AS A TYPE |
| | III-B FIRE SPRINKLERED PROTECTED (1 HOUR FIRE RATING). |
| | SEE 2007 CODE COMMENTARY FBC-B TABLE 601 OFTEN TYPE A |
| | OR B ARE REFEFFED TO AS PROTECTED AND UNPROTECTED |
| | CONSTRUCTION, RESPECTIVELY. PLEASE NOTE THIS |
| | TERMINOLOGY DOES NOT REFER TO WHETHER THE BUILDING IS |
| | SPRINKLERED OR NOT. |
| | THE A REFERS TO REQUIRED FIRE RATINGS FOR EXTERIOR |
| | WALLS PRIMARY STRUCTURAL FRAME, ROOF CONSTRUCTION AND |
| | SECONDARY MEMBERS. 2010 FBC-B TABLE 601 FOOTNOTE B |
| | PROVIDES REDUCTION IN HOURS, A TYPE BUILDING ALL |
| | REQUIRE A MINIMUM OF 1 HOUR FIRE RATING OF ROOF FRAMING |
| | MEMBERS, SEE BUILDING TYPE IIIA FOOTNOTES ,B, C &D. |
| | SHEET A8 THE STRUCTURAL ELEMENTS DOES NOT INDICATE ANY |
| | RATING ON STRUCTURAL MEMBERS. |
| | |
| | 1C) 3RD REQUEST. |
| | WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | STANDPIPES |
| | PRE-ENGINEERED SYSTEMS |
| | FIRE PROTECTION NOTES INDICATE THAT THE BUILDING IS TO |
| | BE FIRE SPRINKLERED, THE 2010 FBC-B 903.2.7 NEW WORK |
| | REQUIRES SPRINKLERS FOR MERCANTILE AREAS WITH A FIRE |
| | AREA GREATER THAN 12,000 SQ FT. NO FIRE SPRINKLER PLANS |
| | WERE SUBMITTED. 107.3.5.1.1( 5) FIRE SUPPRESSION. NOTES |
| | ON THE PLAN DO NOT CONSTITUTE COMPLIANCE WITH THIS |
| | SECTION. THERE HAS TO BE A DESIGN CRITERIA FOR THE |
| | SIZING OF THE UNDER GROUND FIRE MAIN THAT WILL BE |
| | REQUIRED TO COME INTO THIS BUILDING. NO SIZING HAS BEEN |
| | SUBMITTED. |
| | |
| | 1D) NO WRITTEN RESPONCE. 2ND REQUEST, |
| | IS THERE GOING TO BE A NEW ROOF TO BE PUT ON UNDER THIS |
| | PROJECT, IF SO THIS WILL BECOME A LEVEL III ALTERATION |
| | AND WILL AFFECT FUTURE REVIEWS AND CODE REQUIREMENTS, |
| | THERE IS A NOTE THAT THE BACK OF THE BUILDING A NEW |
| | ROOF STRUCTURE AND ROOF TO BE APPLIED. SHEET A-12 NOTE |
| | ONE INDICATES TO ONLY TO REPAIR ALL NEW PENETRATIONS. |
| | REVIEW 2010 EXST BLDG CODE SECTION 611.1.1 NOT MORE |
| | THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION |
| | OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE |
| | REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD |
| | UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION |
| | CONFORMS TO REQUIREMENTS OF THIS CODE. |
| | |
| | 2) SHEET A-3: |
| | 2A-B) COMPLIED> |
| | |
| | 2C) 3D REQUEST. SEMI-COMPLIED. |
| | FRONT ENTRY DOORS, INDICATE THEY ARE HORIZONTAL SLIDING |
| | DOORS, PLEASE PROVIDE COMPLIANCE WITH FBC-B 1008.1.10 / |
| | 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A |
| | GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES |
| | WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E |
| | OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK |
| | UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE, NOT |
| | JUST BREAK AWAY PANELS. SHEET A-7 INDICATES BREAK OUT |
| | PANELS BUT TO DATE NO PRODUCT APPROVALS HAVE BEEN |
| | SUBMITTED SHOWING PANIC OR FIRE EXIT HARDWARE. |
| | |
| | 3) SHEET A-4: |
| | 3A-B) COMPLIED> |
| | |
| | |
| | |
| | |
| | |
| | 3C) COMPLIED. ; |
| | |
| | 4) COMPLIED. |
| | |
| | 5) PROVISO: |
| | SHEET A-8: |
| | 5A) NEW COOLERS AND FREZZERS ARE UNDER SEPARATE PERMIT. |
| | NOT PART OF THIS REVIEW. |
| | |
| | 5B) COMPLIED> |
| | |
| | 6) PROVISO: |
| | SHEET A-9 AWNINGS ARE UNDER A SEPARATE PERMIT, NOT PART |
| | OF THIS REVIEW AS WELL AS SIGNS. |
| | |
| | 7) S1 & S2: |
| | 7A) 3RD REQUEST: |
| | SHEET A-8 & A-11 DETAIL B & E INDICATES BACK OF HOUSE |
| | FREZER LOCATION, EXISTING CBS WALLS W/ NEW ROOF |
| | STRUCTURE AND ROOFING. THE S-1 SHOWS THIS AREA WITH |
| | VARIOUS DETAILS. |
| | 7A)(1) THE EXTERIOR WALL SECTION D/S2 IS A CUT SECTION |
| | THRU THE WALL BUT THE DETAIL IS FOR A HEADER THRU A |
| | WALL OPENING, WRONG DETAIL NOT FOR A WALL SECTION. |
| | 107.2.1.3 DISCREPANCY IN PLANS. |
| | |
| | 7A)(2) NONE OF THE DETAILS ON SHEET S-2 SHOW SIMILAR |
| | WALL, CONCRETE ROOF SECTION AND BEAM TO BE POURED INTO |
| | THE EXISTING CBS WALL AS SHOWN ON SHEET A-8 DETAIL E. |
| | NEITHER IS THERE SHOWN VERTICAL COLUMN PLACEMENT TYING |
| | THE FOOTER THRU TO THE ROOF SLAB MAKING THE MWFRS MAIN |
| | WIND FORCE RESISTING SYSTEM. MISSING DETAILS OR |
| | MISLABELED. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 7A)(3) SHEET S-1 THE CHICKEN COOLER & FREZZER DOES NOT |
| | HAVE ANY WALL TAGS IDENTIYING DWTAILS FOR CONSTRUCTION, |
| | COLUMNS, BEAMS & ROOF FRAMING/ SLAB MEMBERS. MISSING |
| | DETAILS OR MISLABELED. 107.2.1.3 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 7B) COMPLIED> |
| | |
| | 8) COMPLIED> |
| | |
| | 9) 2ND REQUEST ,2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR AUTOMATIC BYPASS DOORS SEMI COMPLIED, |
| | THE PRODUCT APPROVAL IS FOR BREAK AWAY DOORS BUT THEY |
| | DO NOT COMPLY WITH |
| | 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING |
| | ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN |
| | A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A |
| | LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | |
| | (D) ROOFING SYSTEMS, NO PRODUCT APPROVALS FOR WOOD |
| | DECKS |
| | |
| | NOA 13-0424.11 |
| | P-12 |
| | DECK TYPE:31 CONRETE DECK, INSULATED |
| | MAX DESIGN PRESS: -162 PSF LIMITAQTION #9 |
| | FOR RECOVER VERIFY ONLY ONE ROOF & PULL TEST |
| | |
| | (G) NO PRODUCT APPROVALS SUBMITTED. PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 10) THE FOLLOWING ITEMS WILL DEAL WITH ROOFING REPORTS |
| | BE ADVISED OF THE INFORMATION THAT WILL NEED TO BE |
| | HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING |
| | DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE |
| | WITH THE FOLLOW ITEMS: |
| | (FLAT ROOF) NEW FLAT ROOF OVER FREZZER COMPARTMENT. |
| | ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___ |
| | CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED. |
| | ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___ |
| | . |
| | ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED |
| | , SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | 11) NEW COMMENT. SHEET A-9 THE NORTH ELEVATION SHOWS A |
| | EXTERIOR WALL MOUNED LADDER THAT ALLOWS ENTRY INTO THE |
| | MECHANICAL MEZZANINE. THE PLANS DO NOT INDICATE HOW |
| | ACCESS TO THE ROOF TOP A/C UNITS. 2010 FBC-B 1509.6 |
| | EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| | STRUCTURES. |
| | WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| | INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| | EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| | PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| | EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| | THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| | ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30 INCHES (762 MM) HIGH. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |