| 2014-02-25 08:31:51 | PLUMBING PLAN REVIEW | | | PERMIT: 13090329 | | | ADD: 5011 BROADWAY | | | CONT: TO BE DETERMINED | | | TEL: (305)331-1400 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE | | | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 | | | EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2ND REVIEW | | | DATE: TUE. FEB. 25 | | | ACTION: DENIED | | | | | | 1) 2ND REQUEST, | | | SHEET P-1 PLEASE PROVIDE CALCULATIONS FOR THE SIZING OF | | | THE GREASE INTERCEPTOR SIZE. 2010 FBC-PLUMBING TABLE | | | 1003.5.1. | | | | | | 2) COMPLIED. | | | | | | 3) THE FISH FREEZER IS NOT INDICATED TO HAVE A TRAP | | | PRIMER NOR ANY OTHER WASTE WATER THAT WOULD PROVIDE | | | LIQUIDS TO SEAL THE TRAP. | | | 2010 FBC-P 1002.4 TRAP SEALS. | | | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS | | | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 | | | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO | | | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO | | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE | | | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A | | | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR | | | ASSE 1044. | | | | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|