| Date |
Text |
| 2014-11-04 09:39:52 | 11/3/2014 |
| | PROJECT: TROPICAL SUPERMARKET |
| | PERMIT#: 13090329 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) RISER DIAGRAM AND PANEL SCHEDULES DOES NOT MATCH UP |
| | WITH RISER DIAGRAM KEY NOTES. VOLTAGE OF ELECTRICAL |
| | SYSTEM IN NOTE A IS INDICATED AT 277/480V 3PH 4 WIRE |
| | BUT EVERYWHERE ELSE IS INDICATED AT 120/208V 3PH 4 |
| | WIRE. REVISE PLANS ACORDINGLY. 2010 WPB AMENDMENTS TO |
| | THE FBC 107.2.1 |
| | |
| | 2) THE RISER DIAGRAM KEY NOTES, LETTER AND NUMBER |
| | IDENTIFICATION MARKERS ARE BARELY LEGIBLE. |
| | CLARIFICATION REQUIRED. 2010 WPB AMENDMENTS TO THE FBC |
| | 107.2.1 |
| | |
| | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | 5) CLARIFY LOCATION AND SOURCE FOR ROOFTOP |
| | REFRIGERATION RACK DISCONNECT. RISER DIAGRAM INDICATES |
| | A TAP RULE IS UTILIZED TO FEED AN 800AMP DISCONNECT |
| | FROM A 1600AMP MTS GROUPED WITH SERVICE EQUIPMENT THAT |
| | THEN FEEDS THE REFRIGERATION RACK. CLARIFICATION IS |
| | REQUIED. INDICATE ON THE ELECTRICAL PLANS, WHERE IS THE |
| | REFRIGERATION RACK DISCONNECT LOCATED? HOW IS IT FED |
| | AND FROM WHERE? 2010 WPB AMENDMENTS TO THE FBC 107.2.1 |
| | |
| | 6) VERIFY SUFFICIENT ACCESS AND WORKING SPACE IS |
| | PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT, |
| | SPECIFICALLY AT THE MEZNINNINE, TO PERMIT READY AND |
| | SAFE OPERATION AND MAINTENANCE OF SUCH EQUIPMENT. NEC |
| | 110.26 |
| | |
| | 7) PROVIDE A COMPLETE LIGHTING SUMMARY INDICATING |
| | COMPLIANCE WITH THE FBC ENERGY CONSERVATION 505.3. |
| | |
| | 8) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 |
| | |
| | 9) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT |
| | SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. |
| | EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT |
| | EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL |
| | BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND |
| | BY ONE OF THE WIRING METHODS OF NEC CHAPTER 3. NEC |
| | 700.12(F) |
| | |
| | 10) VERIFY ALL ELECTRIC UNDER THE HOOD TO BE |
| | DISONNECTED UPON ACTIVATION OF THE FIRE SUPRESSION |
| | SYSTEM. NFPA 1, SECTION 50.4.6.1 |
| | |
| | 11) PROVIDE THE SIGN WITH AT LEAST ONE OUTLET SUPPLIED |
| | BY A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| | SUPPLIES NO OTHER LOAD. NEC 600.5 |
| | |
| | 12) VERIFY THE SIGN HAS AN EXTERNALLY OPERABLE SWITCH |
| | OR CIRCUIT BREAKER THAT WILL OPEN ALL UNGROUNDED |
| | CONDUCTORS WITHIN SIGHT OF THE SIGN OR OUTLINE LIGHTING |
| | SYSTEM THAT IT CONTROLS. NEC 600.6(A)(1) |
| | |
| | 13) VERIFY THE SIGN IS CONTROLLED BY A TIMER AS |
| | REQUIRED BY FBC-E 505.2.4. |
| | |
| | 14) PROVIDE A DEDICATED BRANCH CIRCUIT FOR THE FIRE |
| | ALARM SYSTEM. NFPA 72, 10.5.5 |
| | |
| | 15) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | IS REQUIRED FOR GENERATOR, HOOD, FIRE ALARM, SECURITY |
| | SYSTEM, CCTV, ACCESS CONTROL, NETWORK, POS, AND |
| | COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| 2014-10-15 11:41:01 | NEW SHEETS SUBMITTED. JG. |