Plan Review Notes
Plan Review Notes For Permit 13090329
Permit Number 13090329
Review Stop E
Sequence Number 2
Notes
Date Text
2014-11-04 09:39:5211/3/2014
 PROJECT: TROPICAL SUPERMARKET
 PERMIT#: 13090329
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) RISER DIAGRAM AND PANEL SCHEDULES DOES NOT MATCH UP
 WITH RISER DIAGRAM KEY NOTES. VOLTAGE OF ELECTRICAL
 SYSTEM IN NOTE A IS INDICATED AT 277/480V 3PH 4 WIRE
 BUT EVERYWHERE ELSE IS INDICATED AT 120/208V 3PH 4
 WIRE. REVISE PLANS ACORDINGLY. 2010 WPB AMENDMENTS TO
 THE FBC 107.2.1
  
 2) THE RISER DIAGRAM KEY NOTES, LETTER AND NUMBER
 IDENTIFICATION MARKERS ARE BARELY LEGIBLE.
 CLARIFICATION REQUIRED. 2010 WPB AMENDMENTS TO THE FBC
 107.2.1
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) CLARIFY LOCATION AND SOURCE FOR ROOFTOP
 REFRIGERATION RACK DISCONNECT. RISER DIAGRAM INDICATES
 A TAP RULE IS UTILIZED TO FEED AN 800AMP DISCONNECT
 FROM A 1600AMP MTS GROUPED WITH SERVICE EQUIPMENT THAT
 THEN FEEDS THE REFRIGERATION RACK. CLARIFICATION IS
 REQUIED. INDICATE ON THE ELECTRICAL PLANS, WHERE IS THE
 REFRIGERATION RACK DISCONNECT LOCATED? HOW IS IT FED
 AND FROM WHERE? 2010 WPB AMENDMENTS TO THE FBC 107.2.1
  
 6) VERIFY SUFFICIENT ACCESS AND WORKING SPACE IS
 PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT,
 SPECIFICALLY AT THE MEZNINNINE, TO PERMIT READY AND
 SAFE OPERATION AND MAINTENANCE OF SUCH EQUIPMENT. NEC
 110.26
  
 7) PROVIDE A COMPLETE LIGHTING SUMMARY INDICATING
 COMPLIANCE WITH THE FBC ENERGY CONSERVATION 505.3.
  
 8) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
  
 9) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF NEC CHAPTER 3. NEC
 700.12(F)
  
 10) VERIFY ALL ELECTRIC UNDER THE HOOD TO BE
 DISONNECTED UPON ACTIVATION OF THE FIRE SUPRESSION
 SYSTEM. NFPA 1, SECTION 50.4.6.1
  
 11) PROVIDE THE SIGN WITH AT LEAST ONE OUTLET SUPPLIED
 BY A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. NEC 600.5
  
 12) VERIFY THE SIGN HAS AN EXTERNALLY OPERABLE SWITCH
 OR CIRCUIT BREAKER THAT WILL OPEN ALL UNGROUNDED
 CONDUCTORS WITHIN SIGHT OF THE SIGN OR OUTLINE LIGHTING
 SYSTEM THAT IT CONTROLS. NEC 600.6(A)(1)
  
 13) VERIFY THE SIGN IS CONTROLLED BY A TIMER AS
 REQUIRED BY FBC-E 505.2.4.
  
 14) PROVIDE A DEDICATED BRANCH CIRCUIT FOR THE FIRE
 ALARM SYSTEM. NFPA 72, 10.5.5
  
 15) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR GENERATOR, HOOD, FIRE ALARM, SECURITY
 SYSTEM, CCTV, ACCESS CONTROL, NETWORK, POS, AND
 COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
2014-10-15 11:41:01NEW SHEETS SUBMITTED. JG.