| 2014-02-25 06:04:43 | BUILDING PLAN REVIEW |
| | PERMIT: 13090329 |
| | ADD: 5011 BROADWAY |
| | CONT: TO BE DETERMINED |
| | TEL: (305)331-1400 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUE. FEB. 25 |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) SHEET A-1: |
| | 1A) COMPLIED> |
| | MISSING TO WHAT EDITION OF CODE THIS BUILDING DESIGN |
| | AND PERMIT WERE DESIGNED TO, 2010 FBC-B, 2010 FL |
| | EXISTING BUILDING CODE & 2010 FL ACCESSIBILITY CODE, |
| | 1B) 2ND REQUEST: |
| | OCCUPANCY, EXIT & PLUMBING FACILITY DATA, MISSING THE |
| | MINIMUM BUILDING TYPE OF CONSTRUCTION 107.3.5.1.1(3) |
| | TABLE 503. |
| | LIFE SAFETY SHEET LS1 INDICATES THIS BUILDING IS |
| | DESIGNED AS A TYPE III PROTECTED (1 HOUR FIRE RATING) |
| | SEE FBC-B TABLE 601 FOR REQUIRED FIRE RATINGS FOR |
| | EXTERIOR WALLS PRIMARY STRUCTURAL FRAME, ROOF |
| | CONSTRUCTION AND SECONDARY MEMBERS. 2010 FBC-B TABLE |
| | 601 FOOTNOTE B PROVIDES REDUCTION IN HOURS, A TYPE |
| | BUILDING ALL REQUIRE A MINIMUM OF 1 HOUR FIRE RATING OF |
| | ROOF FRAMING MEMBERS, SEE BUILDING TYPE IIIA FOOTNOTES |
| | ,B, C &D. |
| | SHEET A8 DOES NOT INDICATE ANY RATING ON STRUCTURAL |
| | MEMBERS. |
| | |
| | 1C) 2ND REQUEST. |
| | WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | STANDPIPES |
| | PRE-ENGINEERED SYSTEMS |
| | FIRE PROTECTION NOTES INDICATE THAT THE BUILDING IS TO |
| | BE FIRE SPRINKLERED, THE 2010 FBC-B 903.2.7 NEW WORK |
| | REQUIRES SPRINKLERS FOR MERCANTILE AREAS WITH A FIRE |
| | AREA GREATER THAN 12,000 SQ FT. NO FIRE SPRINKLER PLANS |
| | WERE SUBMITTED. 107.3.5.1.1( 5) FIRE SUPPRESSION. |
| | |
| | 1D) 2ND REQUEST, |
| | IS THERE GOING TO BE A NEW ROOF TO BE PUT ON UNDER THIS |
| | PROJECT, IF SO THIS WILL BECOME A LEVEL III ALTERATION |
| | AND WILL AFFECT FUTURE REVIEWS AND CODE REQUIREMENTS, |
| | THERE IS A NOTE THAT THE BACK OF THE BUILDING A NEW |
| | ROOF STRUCTURE AND ROOF TO BE APPLIED. SHEET A-12 NOTE |
| | ONE INDICATES TO ONLY TO REPAIR ALL NEW PENETRATIONS. |
| | REVIEW 2010 EXST BLDG CODE SECTION 611.1.1 NOT MORE |
| | THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION |
| | OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE |
| | REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD |
| | UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION |
| | CONFORMS TO REQUIREMENTS OF THIS CODE. |
| | |
| | 2) SHEET A-3: |
| | 2A-B) COMPLIED> |
| | |
| | 2C) 2ND REQUEST, |
| | FRONT ENTRY DOORS, INDICATE THEY ARE HORIZONTAL SLIDING |
| | DOORS, PLEASE PROVIDE COMPLIANCE WITH FBC-B 1008.1.10 / |
| | 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A |
| | GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES |
| | WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E |
| | OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK |
| | UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 3) SHEET A-4: |
| | 3A-B) COMPLIED> |
| | |
| | 3C) 2ND REQUEST; |
| | NOTE 88 INDICATES THE USE OF PROPANE TANKS ON SITE (2) |
| | 100 GALLON ABOVE GROUND LP TANKS. [F] 414.6 OUTDOOR |
| | STORAGE, DISPENSING AND USE. |
| | THE OUTDOOR STORAGE, DISPENSING AND USE OF HAZARDOUS |
| | MATERIALS SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | PLEASE PROVIDE MSDS SHEETS. F] 414.6.1 WEATHER |
| | PROTECTION. |
| | WHERE WEATHER PROTECTION IS PROVIDED FOR SHELTERING |
| | OUTDOOR HAZARDOUS MATERIAL STORAGE OR USE AREAS, SUCH |
| | AREAS SHALL BE CONSIDERED OUTDOOR STORAGE OR USE WHEN |
| | THE WEATHER PROTECTION STRUCTURE COMPLIES WITH SECTIONS |
| | 414.6.1.1 THROUGH 414.6.1.3. |
| | |
| | 4) COMPLIED> |
| | |
| | 5) PROVISO: |
| | SHEET A-8: |
| | 5A) NEW COOLERS AND FREZZERS ARE UNDER SEPARATE PERMIT. |
| | NOT PART OF THIS REVIEW. |
| | |
| | 5B) COMPLIED> |
| | |
| | 6) PROVISO: |
| | SHEET A-9 AWNINGS ARE UNDER A SEPARATE PERMIT, NOT PART |
| | OF THIS REVIEW AS WELL AS SIGNS. |
| | |
| | 7) S1 & S2: |
| | 7A) 2ND REQUEST: |
| | NEITHER S1 OR S2 SHOW A NEW ROOFING SYSTEM, SHEET A-8 & |
| | A-11 DETAIL A INDICATES BACK OF HOUSE FREZER LOCATION, |
| | EXISTING CBS WALLS W/ NEW ROOF STRUCTURE AND ROOFING. |
| | PART OF THE MWFRS NO INFORMATION AS TO DESIGN ON ANY |
| | ARCHITECTURAL NOR STRUCTURAL SHEETS. |
| | |
| | 7B) COMPLIED> |
| | |
| | 8) COMPLIED> |
| | |
| | 9) 2ND REQUEST ,2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR AUTOMATIC BYPASS DOORS SEMI COMPLIED, |
| | THE PRODUCT APPROVAL IS FOR BREAK AWAY DOORS BUT THEY |
| | DO NOT COMPLY WITH |
| | 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING |
| | ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN |
| | A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A |
| | LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | |
| | (D) ROOFING SYSTEMS |
| | NO PRODUCT APPROVALS FOR WOOD DECKS |
| | |
| | NOA 13-0424.11 |
| | P-12 |
| | DECK TYPE:31 CONRETE DECK, INSULATED |
| | MAX DESIGN PRESS: -162 PSF LIMITAQTION #9 |
| | FOR RECOVER VERIFY ONLY ONE ROOF & PULL TEST |
| | |
| | (G) NO PRODUCT APPROVALS SUBMITTED. PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 10) THE FOLLOWING ITEMS WILL DEAL WITH ROOFING REPORTS |
| | BE ADVISED OF THE INFORMATION THAT WILL NEED TO BE |
| | HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING |
| | DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE |
| | WITH THE FOLLOW ITEMS: |
| | (FLAT ROOF) |
| | ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT. |
| | ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___ |
| | CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED. |
| | ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___ |
| | . |
| | ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD |
| | THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS |
| | DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED |
| | , SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE |
| | SUBMITTED. |
| | ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO |
| | ENHANCED FASTENING ALLOWED. |
| | |
| | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |