Plan Review Notes
Plan Review Notes For Permit 13090329
Permit Number 13090329
Review Stop B
Sequence Number 2
Notes
Date Text
2014-02-25 06:04:43BUILDING PLAN REVIEW
 PERMIT: 13090329
 ADD: 5011 BROADWAY
 CONT: TO BE DETERMINED
 TEL: (305)331-1400
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUE. FEB. 25
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) SHEET A-1:
 1A) COMPLIED>
 MISSING TO WHAT EDITION OF CODE THIS BUILDING DESIGN
 AND PERMIT WERE DESIGNED TO, 2010 FBC-B, 2010 FL
 EXISTING BUILDING CODE & 2010 FL ACCESSIBILITY CODE,
 1B) 2ND REQUEST:
 OCCUPANCY, EXIT & PLUMBING FACILITY DATA, MISSING THE
 MINIMUM BUILDING TYPE OF CONSTRUCTION 107.3.5.1.1(3)
 TABLE 503.
 LIFE SAFETY SHEET LS1 INDICATES THIS BUILDING IS
 DESIGNED AS A TYPE III PROTECTED (1 HOUR FIRE RATING)
 SEE FBC-B TABLE 601 FOR REQUIRED FIRE RATINGS FOR
 EXTERIOR WALLS PRIMARY STRUCTURAL FRAME, ROOF
 CONSTRUCTION AND SECONDARY MEMBERS. 2010 FBC-B TABLE
 601 FOOTNOTE B PROVIDES REDUCTION IN HOURS, A TYPE
 BUILDING ALL REQUIRE A MINIMUM OF 1 HOUR FIRE RATING OF
 ROOF FRAMING MEMBERS, SEE BUILDING TYPE IIIA FOOTNOTES
 ,B, C &D.
 SHEET A8 DOES NOT INDICATE ANY RATING ON STRUCTURAL
 MEMBERS.
  
 1C) 2ND REQUEST.
 WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 FIRE PROTECTION NOTES INDICATE THAT THE BUILDING IS TO
 BE FIRE SPRINKLERED, THE 2010 FBC-B 903.2.7 NEW WORK
 REQUIRES SPRINKLERS FOR MERCANTILE AREAS WITH A FIRE
 AREA GREATER THAN 12,000 SQ FT. NO FIRE SPRINKLER PLANS
 WERE SUBMITTED. 107.3.5.1.1( 5) FIRE SUPPRESSION.
  
 1D) 2ND REQUEST,
 IS THERE GOING TO BE A NEW ROOF TO BE PUT ON UNDER THIS
 PROJECT, IF SO THIS WILL BECOME A LEVEL III ALTERATION
 AND WILL AFFECT FUTURE REVIEWS AND CODE REQUIREMENTS,
 THERE IS A NOTE THAT THE BACK OF THE BUILDING A NEW
 ROOF STRUCTURE AND ROOF TO BE APPLIED. SHEET A-12 NOTE
 ONE INDICATES TO ONLY TO REPAIR ALL NEW PENETRATIONS.
 REVIEW 2010 EXST BLDG CODE SECTION 611.1.1 NOT MORE
 THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION
 OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE
 REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD
 UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION
 CONFORMS TO REQUIREMENTS OF THIS CODE.
  
 2) SHEET A-3:
 2A-B) COMPLIED>
  
 2C) 2ND REQUEST,
 FRONT ENTRY DOORS, INDICATE THEY ARE HORIZONTAL SLIDING
 DOORS, PLEASE PROVIDE COMPLIANCE WITH FBC-B 1008.1.10 /
 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A
 GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES
 WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E
 OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
 UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 3) SHEET A-4:
 3A-B) COMPLIED>
  
 3C) 2ND REQUEST;
 NOTE 88 INDICATES THE USE OF PROPANE TANKS ON SITE (2)
 100 GALLON ABOVE GROUND LP TANKS. [F] 414.6 OUTDOOR
 STORAGE, DISPENSING AND USE.
 THE OUTDOOR STORAGE, DISPENSING AND USE OF HAZARDOUS
 MATERIALS SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
 PLEASE PROVIDE MSDS SHEETS. F] 414.6.1 WEATHER
 PROTECTION.
 WHERE WEATHER PROTECTION IS PROVIDED FOR SHELTERING
 OUTDOOR HAZARDOUS MATERIAL STORAGE OR USE AREAS, SUCH
 AREAS SHALL BE CONSIDERED OUTDOOR STORAGE OR USE WHEN
 THE WEATHER PROTECTION STRUCTURE COMPLIES WITH SECTIONS
 414.6.1.1 THROUGH 414.6.1.3.
  
 4) COMPLIED>
  
 5) PROVISO:
 SHEET A-8:
 5A) NEW COOLERS AND FREZZERS ARE UNDER SEPARATE PERMIT.
 NOT PART OF THIS REVIEW.
  
 5B) COMPLIED>
  
 6) PROVISO:
 SHEET A-9 AWNINGS ARE UNDER A SEPARATE PERMIT, NOT PART
 OF THIS REVIEW AS WELL AS SIGNS.
  
 7) S1 & S2:
 7A) 2ND REQUEST:
 NEITHER S1 OR S2 SHOW A NEW ROOFING SYSTEM, SHEET A-8 &
 A-11 DETAIL A INDICATES BACK OF HOUSE FREZER LOCATION,
 EXISTING CBS WALLS W/ NEW ROOF STRUCTURE AND ROOFING.
 PART OF THE MWFRS NO INFORMATION AS TO DESIGN ON ANY
 ARCHITECTURAL NOR STRUCTURAL SHEETS.
  
 7B) COMPLIED>
  
 8) COMPLIED>
  
 9) 2ND REQUEST ,2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR AUTOMATIC BYPASS DOORS SEMI COMPLIED,
 THE PRODUCT APPROVAL IS FOR BREAK AWAY DOORS BUT THEY
 DO NOT COMPLY WITH
 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 (D) ROOFING SYSTEMS
 NO PRODUCT APPROVALS FOR WOOD DECKS
  
 NOA 13-0424.11
 P-12
 DECK TYPE:31 CONRETE DECK, INSULATED
 MAX DESIGN PRESS: -162 PSF LIMITAQTION #9
 FOR RECOVER VERIFY ONLY ONE ROOF & PULL TEST
  
 (G) NO PRODUCT APPROVALS SUBMITTED. PRE-ENGINEERED A/C
 STANDS
  
 10) THE FOLLOWING ITEMS WILL DEAL WITH ROOFING REPORTS
 BE ADVISED OF THE INFORMATION THAT WILL NEED TO BE
 HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE
 WITH THE FOLLOW ITEMS:
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___
 .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED
 , SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676