2013-09-18 13:55:04FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P-1: PLEASE PROVIDE CALCULATIONS FOR THE
 GREASE INTERCEPTOR SIZE.
 *NOTE: A 750 GALLON GREASE INTERCEPTOR WILL TYPICALLY
 REQUIRE 30 MINUTES RETENTION TIME ALLOWING 25 GALLONS
 FLOW. WITH THE AMOUNT OF DRAINS CONNECTED, THERE
 APPEARS TO BE MORE THAN 25 GALLONS PER MINUTE FLOW TO
 THE GREASE INTERCEPTOR.
  
 2. SHEET P-1 & P-2: AN AIR GAP IS REQUIRED FOR THE
 DAIRY, FISH, MEAT, PRODUCE, AND KITCHEN COOLER FLOOR
 DRAINS OR EXCEPTION.
 802.1.2 FLOOR DRAINS IN FOOD STORAGE AREAS.
 FLOOR DRAINS LOCATED WITHIN WALK-IN REFRIGERATORS OR
 FREEZERS IN FOOD SERVICE AND FOOD ESTABLISHMENTS SHALL
 BE INDIRECTLY CONNECTED TO THE SANITARY DRAINAGE SYSTEM
 BY MEANS OF AN AIR GAP. WHERE A FLOOR DRAIN IS LOCATED
 WITHIN AN AREA SUBJECT TO FREEZING, THE WASTE LINE
 SERVING THE FLOOR DRAIN SHALL NOT BE TRAPPED AND SHALL
 INDIRECTLY DISCHARGE INTO A WASTE RECEPTOR LOCATED
 OUTSIDE OF THE AREA SUBJECT TO FREEZING.
  
 EXCEPTION: WHERE PROTECTED AGAINST BACKFLOW BY A
 BACKWATER VALVE, SUCH FLOOR DRAINS SHALL BE INDIRECTLY
 CONNECTED TO THE SANITARY DRAINAGE SYSTEM BY MEANS OF
 AN AIR BREAK OR AN AIR GAP.
  
 3. FLOOR DRAINS THAT ARE NOT WASTE RECEIVERS REQUIRE
 TRAP PRIMERS.
 1002.4 TRAP SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
 4. SHEET P-4 ALL HOSE BIBBS WILL REQUIRE SEPARATE SHUT
 OFF VALVES.
 606.2 LOCATION OF SHUTOFF VALVES.
 ...ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER
 THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  