| Plan Review Notes For Permit 13090329 |
| Permit Number |
13090329 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-10 10:26:53 | PLANS DENIED | | | 1) EXHAUST FAN #4 IS NOT ON VENTILATION | | | SCHEDULE. PAGE M-4 OF THE PLAN. | | | 2) PLAN SHOW EXHAUST FAN 4 DISCHARGING | | | OVER FISH COOLER ON PAGE M-1 OF PLAN. | | | REFER TO SECTION 501.2 EXHAUST DISCHARGE | | | 2010 FBC (M) | | | 3) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | | ( FOR FRESH AIR AND EXHAUST) 2010 FLORIDA ENERGY CODE. | | | 4) HOOD AND COOLERS AND REFRIGERATION REQUIRE SEPARATE | | | APPLICATION PLANS AND PERMITS | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|