2013-10-10 10:26:53PLANS DENIED
 1) EXHAUST FAN #4 IS NOT ON VENTILATION
 SCHEDULE. PAGE M-4 OF THE PLAN.
 2) PLAN SHOW EXHAUST FAN 4 DISCHARGING
 OVER FISH COOLER ON PAGE M-1 OF PLAN.
 REFER TO SECTION 501.2 EXHAUST DISCHARGE
 2010 FBC (M)
 3) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 ( FOR FRESH AIR AND EXHAUST) 2010 FLORIDA ENERGY CODE.
 4) HOOD AND COOLERS AND REFRIGERATION REQUIRE SEPARATE
 APPLICATION PLANS AND PERMITS