2013-09-18 14:28:53FBC 2010 FUEL GAS REVIEW #1
 DENIED:
  
 1. SHEET P-4: PLEASE SHOW THE POSITION OF THE 2ND STAGE
 REGULATOR.
  
 2. SHEET P-4: PLEASE INCLUDE THE FBC 2010 FUEL GAS CODE
 TABLE USED FOR THE GAS CALCULATIONS. IF TABLE 402.4(26)
 IS BEING USED, THE SUPPLY PIPE WOULD REQUIRE 1" PIPE
 FOR 542,000 BTU AT 30 FEET.
  