| Plan Review Notes For Permit 13090329 |
| Permit Number |
13090329 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-18 14:28:53 | FBC 2010 FUEL GAS REVIEW #1 | | | DENIED: | | | | | | 1. SHEET P-4: PLEASE SHOW THE POSITION OF THE 2ND STAGE | | | REGULATOR. | | | | | | 2. SHEET P-4: PLEASE INCLUDE THE FBC 2010 FUEL GAS CODE | | | TABLE USED FOR THE GAS CALCULATIONS. IF TABLE 402.4(26) | | | IS BEING USED, THE SUPPLY PIPE WOULD REQUIRE 1" PIPE | | | FOR 542,000 BTU AT 30 FEET. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|