| Plan Review Notes For Permit 13090329 |
| Permit Number |
13090329 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-20 14:16:43 | 5011 BROADWAY | | | PERMIT # | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND | | | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF | | | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE | | | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE | | | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL | | | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO | | | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE | | | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. | | | 2. UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION | | | OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS | | | 3. PER NFPA 101, 2010 ED - 36.2.5.2.1 DEAD-END | | | CORRIDORS ARE NOT TO EXCEED 20 FT. | | | 4. SHOW LOCATION OF TYPE K FIRE EXTINGUISHER. | | | 5.PLANS INDICATE THAT THE BUILDING WILL HAVE AN | | | APPROVED AUTOMATIC SUPERVISED SPRINKLER SYSTEM, BUT NO | | | SPRINKLER LAYOUT IS PROVIDED. | | | | | | | | | LAUREN PHILMORE | | | FIRE INSPECTOR II / INVESTIGATOR I | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4783 | | | | | | |
|