Plan Review Notes
Plan Review Notes For Permit 13090299
Permit Number 13090299
Review Stop B
Sequence Number 2
Notes
Date Text
2013-09-25 14:46:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PROVIDE A COPY OF THE TEST REPORT FOR THIS PRODUCT.
  
 2ND REVIEW - TESTED ASSEMBLY INCLUDES A SUSPENDED
 GYPSUM CEILING. THIS IS NOT APPLICABLE FOR YOUR
 INSTALLATION. PROVIDE TEST REPORT WHICH DOES NOT
 INCLUDE THE SUSPENDED CEILING.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PROVIDE A COPY OF THE TEST REPORT FOR THIS PRODUCT.
  
 2ND REVIEW - TESTED ASSEMBLY INCLUDES A SUSPENDED
 GYPSUM CEILING. THIS IS NOT APPLICABLE FOR YOUR
 INSTALLATION. PROVIDE TEST REPORT WHICH DOES NOT
 INCLUDE THE SUSPENDED CEILING.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 2ND REVIEW - PROVIDE A LETTER FROM THE MANUFACTURER
 WHICH GIVES THE COMMITMENT THAT THIS TEST WILL BE DONE
 AS WELL AS AN EXPLANATION AS TO WHY THIS HAS NOT BEEN
 DONE AT THIS TIME. IT IS MY UNDERSTANDING THAT THEY
 AGREED TO THIS IN MAY 2013. IT IS NOT CLEAR WHY THIS
 ISN'T COMPLETED BY NOW, FOUR MONTHS LATER. OTHER
 MANUFACTURERS HAVE PROVIDED TEST RESULTS WITHIN 30 DAYS
 OF COMMITMENT.
  
  
  