Plan Review Notes
Plan Review Notes For Permit 13090267
Permit Number 13090267
Review Stop Z
Sequence Number 1
Notes
Date Text
2013-10-17 21:16:22FAILED
  
 1) THE TRASH COMPACTOR (TC) ADJACENT TO BUILDING J-1 IS
 NOT SCREENED BY THE SERVICE COURT WALL. THIS WAS SHOWN
 IN THE CORRECT LOCATION ON THE CURRENTLY APPROVED
 PERMIT PLAN.
  
 2) A GENERATOR WAS ADDED IN THE SERVICE COURT NORTH OF
 BUILDING J-3. HOW DOES THE CONSTRICTING THE AREA AFFECT
 THE ABILITY TO PROVIDE TRASH AND LOADING FUNCTIONS IN
 THE SERVICE COURT?
  
 3) THE LINE OF SITE PLAN FOR BUILDING J5 NEEDS TO SHOW
 IMPACT OF THE 12.5 TON RTU FROM THE NORTH.
  
 4) THE LINE OF SITE PLAN FOR BUILDING J7 NEEDS TO SHOW
 IMPACT OF THE 12.5 TON RTU FROM THE SOUTH.
  
 5) THE LINE OF SITE PLAN FOR BUILDING J8 NEEDS TO SHOW
 IMPACT OF THE 12.5 TON RTU FROM THE SOUTH AND THE 10
 TON RTUS THAT ARE OVER THE SERVICE BAYS (THE PARAPET
 WALL IS CLOSER TO THE RTU HERE).
  
 6) PLEASE PROVIDE THE HEIGHTS OF THE 20 AND 25 TON
 RTUS.
  
 7) THE EAST ELEVATION FOR BUILDING J6 DOES NOT
 ACURATELY REFLECT THE CHANGES TO THE WEST ELEVATION.
  
 8) SHEEST M216 AND M218 SHOW 2 OF THE RTU HAVING
 DIFFERENT TONAGE THEN THE ROOF PLAN.
  
 9) CHANGES REQUIRED TO BE SHOWN ON THE AS-BUILT SITE
 PLAN AMENDMENT.
  
 A. BLDG J-3 GENERATOR
 B. BLDG J-4 RELOCATED TREES
 C. BLDG J-6 NEW REAR DOOR
 D. BLDG J-7 ENTRY
 E. BLDG J-1 ENTRY BOLLARDS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-09-13 16:14:269/13/13