| 2013-09-18 17:53:51 | 1721 PALM BEACH LAKES BLVD. - 10 BUILDINGS IN MALL | | | PERMIT #13090267 | | | MASTER #12100555 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | *****PROVISO - THE CIVIL/SITE PLANS SHOW THE ENTIRE | | | MALL SITE FOR REFERENCE AND CLARIFICATION PURPOSES | | | ONLY: THE FOLLOWING COMMENTS MAY APPLY TO SITE WORK | | | LOCATED OUTSIDE THE SCOPE OF THIS PERMIT | | | (#12100555).***** | | | | | | REPEAT COMMENTS: | | | SHEET C403 & C405: NO FIRE LANE CURBS OR SIGNS LOCATED | | | ON PLAN FOR "H" BUILDINGS. INDICATE FIRE LANES ON BOTH | | | FRONT AND REAR OF BUILDINGS. | | | | | | SHEET C602: FIRE HYDRANTS WILL NEED TO BE INSTALLED AND | | | MAINTAINED WITH WORKING CLEARANCES OF 7'-6" TO THE | | | FRONT/SIDES AND 4'-0" TO THE REAR. ANY PARKING SPACES | | | LOCATED WITHIN THIS BUFFER ZONE WILL NEED TO BE | | | INDICATED AS "NO PARKING" STALLS. | | | | | | SHEET C602: FIRE DEPARTMENT CONNECTION FOR FUTURE | | | BUILDING "PBA #5" SHALL BE LOCATED WITHIN 150 FEET OF A | | | FIRE HYDRANT. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 |
|