| Plan Review Notes For Permit 13090267 |
| Permit Number |
13090267 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-19 14:02:49 | 13090267 | | | ELECTRIC REVISION FOR PB OUTLET MALL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | VERIFY THE GROUNDING CIRCUIT FOR EMERGENCY LIGHT | | | CIRCUITS #26, 28, 30 LOCATED IN THE 480 V HOUSE PANEL | | | J3 HAS BE PROPERLY SIZED. NEC 250.122 (B) | | | | | | PROVIDE THE LISTING WITH SPECIFICATIONS FOR THE LIGHT | | | POLE ASSEMBLY WITH 200 VA TRANSFORMER POWER SUPPLY | | | SERVING A GFCI RECEPTACLE. NEC 110.3 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | |
|