| Plan Review Notes For Permit 13090267 |
| Permit Number |
13090267 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-12 14:33:22 | NOTE: | | | 1) NOTE: A2.0X FIRE SPRINKLER ROOM X-03 WALL TYPE 100 | | | IS A 1 HR RATED WALL, IF FIRE PUMP IS REQUIRED, A FIRE | | | PUMP ROOM REQUIRES A 2 HR FIRE RATING 2010 FBC-B | | | 913.2.1. |
|