Text |
| 2013-09-16 16:49:59 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SPECIFY THE SIZE AND TYPE OF ALL WINDOWS THAT ARE |
| | BEING REPLACED ON THE PLANS. (IE SINGLE HUNG, |
| | HORIZONTAL SLIDING) CITY AMENDMENTS 107.2.1 AND FBCR |
| | 301.2.1 |
| | |
| | 2) SPECIFY THE SIZE OF THE ARCHED FIXED GLASS WINDOW |
| | ABOVE THE 52" X 50" WINDOW IN THE MASTER BEDROOM. FBCR |
| | 301.2.1 |
| | |
| | 3) SHOW THAT THE NEW BEDROOM WINDOWS WILL COMPLY WITH |
| | FBCR 310 FOR EMERGENCY ESCAPE AND RESCUE OPENINGS. |
| | |
| | 4) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE FOR THE |
| | STRUCTURAL MULLIONS SHOWN AT THE BEDROOM ADJACENT TO |
| | THE GARAGE AND FOR THE CONNECTION OF THE ARCHED F.G. TO |
| | THE MASTER BEDROOM WINDOW. DCA RULE 9N-3 |
| | |
| | 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE DOUBLE |
| | OUTSWING FRENCH DOORS WITH SIDELITES SPECIFIED ON THE |
| | PLANS AT THE FLORIDA ROOM. SPECIFY THE SIZE OF THE |
| | SIDELITES ON THE PLANS. DCA RULE 9N-3 AND FBCR 301.2.1 |
| | |
| | 6) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. ALSO |
| | INDICATE THE SPECIFIC WINDOW OR DOOR SIZE, TYPE OF |
| | GLASS, AND DESIGN PRESSURE LISTED IN THE NOA THAT IS TO |
| | BE INSTALLED. CITY AMENDMENTS 107.3.4.1 AND FBCR |
| | 301.2.1 |
| | |
| | 7) THE 8' X 7' FIXED GLASS WINDOWS AT THE FLORIDA ROOM |
| | ARE LARGER THAN THE MAXIMUM SIZE OF 4' X 8' ALLOWED BY |
| | NOA NO. 13-0502.03 FOR THE PGT F.G. WINDOWS. PLEASE |
| | INDICATE HOW THIS WILL BE RESOLVED. DCA RULE 9N-3 AND |
| | FBCR 301.2.1 |
| | |
| | 8) THE WIND PRESSURES WERE NOT SPECIFIED FOR THE 52" X |
| | 50" WINDOWS W/ ARCH AT THE MASTER BEDROOM AND KITCHEN. |
| | PLEASE CLARIFY. |
| | |
| | 9) IN ORDER TO LESSEN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS HAVE |
| | BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |