| Plan Review Notes For Permit 13090220 |
| Permit Number |
13090220 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-11-05 17:03:58 | ARE PANELBOARD BUS STABS RATED FOR 150A BRANCH BREAKER? | | | PLAN SHOWS STAIRS TO LEVEL 2 BUT NO DETAILS - ON | | | ORIGINAL SUBMISSION | | | DEPENDING ON CONFIGURATION AND LAYOUT, ADDITONAL EM | | | LIGHTS MAY BE REQUIRED FOR SAFETY AROUND MACHINERY AND | | | FOR EXITING | | | WHERE IS PANEL A-2-C AND WHAT ARE THE LOADS? - ON | | | ORIGINAL SUBMISSION | | | ELECTRICAL LOAD CALCULATION REQUIRED SHOWING MOTOR | | | LOADS, MACHINERY LABELS AND LOADS, CONTINUOUS LOADS AT | | | 125% | | | PROVIDE ENERGY CODE CALCULATION FOR ENERGY BUDGET AND | | | CONSUMPTION | | | SMOKE DETECTORS ARE SHOWN ON PLANS AND NO FACP IS | | | INDICATED, PLEASE EXPLAIN THE DESIGN OF THE SYSTEM | | | #6 CONDUCTORS NOT RATED 80 AMPS (MILL #1) | | | WATER FOUNTAIN RECEPTACLE TO BE INDICATED AS GFCI OR | | | GFCI PROTECTED |
|