| Plan Review Notes For Permit 13090195 |
| Permit Number |
13090195 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-10 14:10:44 | BUILDING PLAN REVIEW | | | REVISION: 13090195 | | | PERMIT: 13080592 | | | ADD: 3800 WASHINGTON RD | | | CONT: JTL AIR CONDITIONING & REFRIGARATION | | | TEL: (954)448-1360 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: SEPT 10/ 2013 | | | ACTION: DENIED | | | | | | 1) THIS SHAFT IS LOCATED IN A HIGHRISE BUILDING, THE | | | MINIMUM BUILDING TYPE IB, FBC-B 503. THE 2010 FBC-B | | | 708.12 ENCLOSURES AT THE TOP. A SHAFT ENCLOSURE THAT | | | DOES NOT EXTEND TO THE UNDERSIDE OF THE ROOF SHEATHING, | | | DECK OR SLAB OF THE BUILDING SHALL BE ENCLOSED AT THE | | | TOP WITH CONSTRUCTION OF THE SAME FIRE RESISTANE AS THE | | | TOP MOST FLOOR PENETRATION BY THE SHAFT, BUT NOT LESS | | | THAN THE FIRE-RESISTANCE RATING REQUIRED FOR THE SHAFT | | | ENCLOSURE. FBC-B TABLE 601 REQUIRES A 2 HR FLOOR RAING. | | | | | | 2) PLANS DO NOT SHOW THE A/C DUCT PENETRATING THE TOP | | | OF THE SHAFT, FIRE DAMPERS WILL ALSO BE REQUIRED AND | | | STEEL FLANGES TO TRANSITION FROM THE FLOOR PLATE TO | | | METAL DUCT. FBC-B 716.5.3. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|