2013-09-10 14:10:44BUILDING PLAN REVIEW
 REVISION: 13090195
 PERMIT: 13080592
 ADD: 3800 WASHINGTON RD
 CONT: JTL AIR CONDITIONING & REFRIGARATION
 TEL: (954)448-1360
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPT 10/ 2013
 ACTION: DENIED
  
 1) THIS SHAFT IS LOCATED IN A HIGHRISE BUILDING, THE
 MINIMUM BUILDING TYPE IB, FBC-B 503. THE 2010 FBC-B
 708.12 ENCLOSURES AT THE TOP. A SHAFT ENCLOSURE THAT
 DOES NOT EXTEND TO THE UNDERSIDE OF THE ROOF SHEATHING,
 DECK OR SLAB OF THE BUILDING SHALL BE ENCLOSED AT THE
 TOP WITH CONSTRUCTION OF THE SAME FIRE RESISTANE AS THE
 TOP MOST FLOOR PENETRATION BY THE SHAFT, BUT NOT LESS
 THAN THE FIRE-RESISTANCE RATING REQUIRED FOR THE SHAFT
 ENCLOSURE. FBC-B TABLE 601 REQUIRES A 2 HR FLOOR RAING.
  
 2) PLANS DO NOT SHOW THE A/C DUCT PENETRATING THE TOP
 OF THE SHAFT, FIRE DAMPERS WILL ALSO BE REQUIRED AND
 STEEL FLANGES TO TRANSITION FROM THE FLOOR PLATE TO
 METAL DUCT. FBC-B 716.5.3.
  