| 2013-09-25 07:22:07 | PLAN SHOWS A 30 KVA XFORMER AND PANEL SCHEDULE SHOWS A | | | 32+KVA DEMAND LOAD | | | ENSURE TIMECLOCK FOR LIGHTING HAS PROGRAMMING CARRYOVER | | | FOR MINIMUM 10 HOURS FBC-EC 505.2 | | | ENSURE FLUORESCENT LIGHTING HAS SEPERABLE DISCONNECTS | | | PER 410.130 (G) | | | LIGHTING CONTROLS TO BE IN FULL COMPLIANCE WITH FBC-EC | | | 505.2 | | | FLUORESCENT FIXTURES TO BE TANDEM WIRED AS APPLICABLE | | | PER FBC-EC 505.3 | | | | | | |
|