| Plan Review Notes For Permit 13090136 |
| Permit Number |
13090136 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-10 17:44:01 | 5829 CORPORATE WAY | | | PERMIT #13090136 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS DO NOT APPEAR TO BE SCALABLE AND THERE IS NO | | | SCALE INDICATED ON THE PLANS. | | | | | | PER NFPA 101 SECTION 12.3.4.3.3, PROVIDE SPEAKER/STROBE | | | NOTIFICATION APPLIANCES AS ASSEMBLY OCCUPANCIES WITH AN | | | OCCUPANT LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE | | | FIRE ALARM NOTIFICATION BY VISIBLE SIGNALS AND VOICE | | | ANNOUNCEMENTS. | | | | | | PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE | | | NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN | | | THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE | | | BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. | | | | | | BATTERY CALCULATIONS INDICATE A BATTERY IN EXCESS OF 9 | | | AMP-HOURS IS NEEDED; HOWEVER, THE PLANS ONLY SHOW A 9 | | | AMP-HOUR BATTERY. | | | | | | INDICATE IF THERE ARE ANY DUCT SMOKE DETECTORS TIED | | | INTO THE FIRE ALARM SYSTEM. DUCT DETECTORS SHALL | | | INITIATE A GENERAL ALARM IN LIEU OF A SUPERVISORY | | | ALARM. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|