Plan Review Notes
Plan Review Notes For Permit 13090136
Permit Number 13090136
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-09-10 17:44:015829 CORPORATE WAY
 PERMIT #13090136
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS DO NOT APPEAR TO BE SCALABLE AND THERE IS NO
 SCALE INDICATED ON THE PLANS.
  
 PER NFPA 101 SECTION 12.3.4.3.3, PROVIDE SPEAKER/STROBE
 NOTIFICATION APPLIANCES AS ASSEMBLY OCCUPANCIES WITH AN
 OCCUPANT LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE
 FIRE ALARM NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 BATTERY CALCULATIONS INDICATE A BATTERY IN EXCESS OF 9
 AMP-HOURS IS NEEDED; HOWEVER, THE PLANS ONLY SHOW A 9
 AMP-HOUR BATTERY.
  
 INDICATE IF THERE ARE ANY DUCT SMOKE DETECTORS TIED
 INTO THE FIRE ALARM SYSTEM. DUCT DETECTORS SHALL
 INITIATE A GENERAL ALARM IN LIEU OF A SUPERVISORY
 ALARM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved