| Plan Review Notes For Permit 13090116 |
| Permit Number |
13090116 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-12 12:33:12 | 310 8TH STREET | | | TRACKING #13090116 | | | PERMIT #13080072 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS DO NOT INDICATE THE LOCATION OF THE ELECTRICAL | | | PANEL FOR UNIT B. | | | | | | NO SMOKE ALARM PROVIDED IN UNIT B. | | | | | | PLANS ONLY INDICATE THERE IS A WATER HEATER FOR UNIT A. | | | IS THIS ACCURATE? | | | | | | ELECTRICAL PANEL "C" APPEARS TO BE RECESSED IN A 1-HOUR | | | FIRE RATED WALL. HOW IS THE INTEGRITY OF THE WALL BEING | | | MAINTAINED? | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|