| Plan Review Notes For Permit 13090100 |
| Permit Number |
13090100 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-18 15:14:55 | FAILED | | | | | | 1) THE PERMIT SHALL INCLUDE THE SIGHT LINE DRAWINGS | | | THAT VERIFY THE ROOFTOP MECHANICAL EQUIPMENT IS | | | SCREENED FROM VIEW. THE DRAWINGS SHALL INCLUDE | | | INFORMATION ON THE SIZE OF THE SPECIFIC ROOFTOP UNIT | | | AND THE HEIGHT, INCLUDING THE CURB OF THE UNITS (MAY BE | | | DONE IN CHART FORM). | | | | | | 2) THE SIGHT LINE DRAWINGS SUPPLIED WITH THE ZONING | | | APPLICATION SHOW NO SCREENING ISSUES, BUT ALSO GIVE NO | | | INFORMATION ON THE SPECIFIC RTU TO CORRELATE THE UNIT | | | SIZE WITH THE UNITS SHOWN ON THE BUILDING PERMIT PLANS. | | | ADDITIONALLY, ONE OF THE UNITS ON BAY B01 IS CLOSER TO | | | THE EDGE OF THE BUILDING ON THE PERMIT THAN AS IT IS | | | SHOWN ON THE ZONING PLANS. | | | | | | 3) PROVIDE A SITE PLAN/SURVEY WHICH SHOWS THE SETBACKS | | | OF THE BUILIDING FROM THE WEST PROPERTY LINE. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2013-09-30 10:25:02 | 9/30/13 |
|