 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE GFP PROTECTION FOR THE ELECTRICAL SERVICE. NEC
 230-95
  
 VERIFY THE ELECTRICAL EQUIPMENT HAS SUFFICIENT
 INTERRUPTING RATING. INDICATE THE ELECTRICAL EQUIPMENT
 INTERRUPTING RATING ON THE PLANS. NEC 110.9
  
 VERIFY REQUIRED ACCESS AND WORKING CLEARANCES HAVE BEEN
 PROVIDED TO THE ELECTRICAL EQUIPMENT. NEC 110.26
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.22, 110.16, 110.22
  
 PROVIDE PANEL SCHEDULES FOR HVB2 AND LVB2.
  
 LIGHTING TIMERS REQUIRE BACKUP PROTECTION. FBC-EC
 505.2.4
  
 VERIFY THE LIGHTING SCENES, SEQUENCING AND CONTROLS
 MEET THE REQUIREMENTS OF FBC ENERGY CODE. FBC-EC 505.2
  
 PROVIDE LIGHTING POWER DENSITY COMPLIANCE CERTIFICATION
 ON ELECTRICAL PLANS. FBC-EC 505.503
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  