| 2013-10-01 11:49:56 | #13090100 | | | 1855 PALM BEACH LAKES BLVD | | | MALL OUT PARCEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE GFP PROTECTION FOR THE ELECTRICAL SERVICE. NEC | | | 230-95 | | | | | | VERIFY THE ELECTRICAL EQUIPMENT HAS SUFFICIENT | | | INTERRUPTING RATING. INDICATE THE ELECTRICAL EQUIPMENT | | | INTERRUPTING RATING ON THE PLANS. NEC 110.9 | | | | | | VERIFY REQUIRED ACCESS AND WORKING CLEARANCES HAVE BEEN | | | PROVIDED TO THE ELECTRICAL EQUIPMENT. NEC 110.26 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.22, 110.16, 110.22 | | | | | | PROVIDE PANEL SCHEDULES FOR HVB2 AND LVB2. | | | | | | LIGHTING TIMERS REQUIRE BACKUP PROTECTION. FBC-EC | | | 505.2.4 | | | | | | VERIFY THE LIGHTING SCENES, SEQUENCING AND CONTROLS | | | MEET THE REQUIREMENTS OF FBC ENERGY CODE. FBC-EC 505.2 | | | | | | PROVIDE LIGHTING POWER DENSITY COMPLIANCE CERTIFICATION | | | ON ELECTRICAL PLANS. FBC-EC 505.503 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | |
|