| 2013-10-03 10:33:49 | BUILDING PLAN REVIEW |
| | PERMIT: 13090100 |
| | ADD: 1855 PALM BEACH LAKES SHELL BII |
| | CONT: EMJ |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: OCT. 03/2013 |
| | ACTION: DENIED |
| | |
| | 1) MISSING SOILS REPORT 2010 FBC-B / 1802.2.1 |
| | QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF |
| | THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY |
| | INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY |
| | WITH THE PROVISIONS OF SECTIONS 1803.3.1 & 1803.6 |
| | REPORTING. |
| | |
| | 2) MISSING RESIDENT INSPECTOR PACKAGE, TILT WALL |
| | REQUIRES A RESIDENT INSPECTOR. FBC* 109.3.7 RESIDENT |
| | INSPECTOR. |
| | SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN |
| | CONRAD MANAGER OFTHE RESIDENT INSPECTOR PROGRAM. A |
| | RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS |
| | PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQ FT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| | OR METHODS OF CONSTRUCTION |
| | KEN CONRAD |
| | TEL 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 3) MISSING. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) MISSING 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, ROOF HATCHES . |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 5) STRUCTURAL SHEET UNDER TTHE COMPONENTS & CLADDING |
| | FIGURES 20 SQ FT MIN IN PRESSURES, FOR THE ROOFING |
| | PRODUCT APPROVAALS WE USE 10 SQ FT WITH THE HIGH |
| | PRESSURES, COMPONENTS & CLADDING 1609.6.4.4.1. |
| | |
| | 6) A112 TENANT SPACE B11 IN THE REAR OF THE BUILDING IN |
| | THE STORAGE ROOM IT APPEARS TO HAVE 2 WALLS THAT |
| | PARTIALLY BLOCKS THE EGRESS PATH, PLEASE SHOW |
| | COMPLIANCE WITH 2010 FBC-B 1014.2.4 EXCEPTION # 2(1-4). |
| | |
| | 7) A142 INDICATES A ROOF HATCH WITHIN 10'-0" OF THE |
| | EDGE OF THE ROOF, SHOW COMPLIANCE WITH 2010 FBC-B |
| | 1013.6. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |