2013-10-18 15:19:20THE FOLLOWING EXCEPTIONS WERE NOTED AND SHALL BE
 CORRECTED FOR INSPECTIONS ON SITE.
 1. AS PER FBCR BECAUSE THERE IS AN ATTACHED GARAGE AS
 WELL AS FOSSIL FUEL BURNING APPLIANCES, THERE SHALL BE
 CARBON MONOXIDE DETECTORS INSTALLED ACCORDING TO CODE.
 2. AS PER NEC 2008, INTER-SYSTEM BONDING TERMINALS ARE
 REQUIRED AT THE SERVICE.
 3. AS PER NEC 2008, THOUGH NO ADDITIONAL LOAD IS TO BE
 CALCULATED THEREFROM, ADDITION LIGHTING CIRCUITS THAN
 THOSE DEPICTED ON THE SUBMITTED PANEL SCHEDULE WILL BE
 REQUIRED.
  
 RETURNED TO BIN R10 FOR FURTHER REVIEWS BY: MA