| Plan Review Notes For Permit 13090099 |
| Permit Number |
13090099 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-18 15:19:20 | THE FOLLOWING EXCEPTIONS WERE NOTED AND SHALL BE | | | CORRECTED FOR INSPECTIONS ON SITE. | | | 1. AS PER FBCR BECAUSE THERE IS AN ATTACHED GARAGE AS | | | WELL AS FOSSIL FUEL BURNING APPLIANCES, THERE SHALL BE | | | CARBON MONOXIDE DETECTORS INSTALLED ACCORDING TO CODE. | | | 2. AS PER NEC 2008, INTER-SYSTEM BONDING TERMINALS ARE | | | REQUIRED AT THE SERVICE. | | | 3. AS PER NEC 2008, THOUGH NO ADDITIONAL LOAD IS TO BE | | | CALCULATED THEREFROM, ADDITION LIGHTING CIRCUITS THAN | | | THOSE DEPICTED ON THE SUBMITTED PANEL SCHEDULE WILL BE | | | REQUIRED. | | | | | | RETURNED TO BIN R10 FOR FURTHER REVIEWS BY: MA |
|