| Plan Review Notes For Permit 13090090 |
| Permit Number |
13090090 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-16 14:50:28 | OVERCURRENT PROTECTION AND DISCONNECTING MEANS TO BE | | | CONTAINED IN SAME ENCLOSURE OR IMMEDIATELY ADJACENT TO | | | EACH OTHER. 230.91, 240.26 | | | PROVIDE INTERSYSTEM BONDING POINT 250.94 | | | PROVIDE DETAILS OF SERVICE BRACING PER FPL SERVICE | | | STANDARDS MANUAL | | | PROVIDE LABELING INFORMATION AND DOT/STATE OF FLORIDA | | | MANUFACTURED BUILDING INFORMATION | | | DEFINE PURPOSE AND USE OF TRAILER | | | DOES THE TRAILER HAVE PLUMBING? PLUMBING PERMIT | | | REQUIRED | | | ENTRY STEPS? IS THIS UNIT ADA EXEMPT? | | | | | | DH |
|