| 2013-11-02 13:27:32 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | COMMENTS FROM PREVIOUS LIST NOT ADDRESSED OR NOT |
| | COMPLIANT WITH FBC 2010 ACCESSIBILITY: |
| | |
| | 1. PROVIDE A LEGIBLE PLAN TO PROVIDE THE FOLLOWING |
| | INFORMATION: |
| | |
| | NUMBER OF ACCESSIBLE SPACES - A TOTAL OF 208 SPACES |
| | SHOWN, 5 ACCESSIBLE. SEE TABLE 208.2, SEVEN ACCESSIBLE |
| | SPACES REQUIRED. |
| | LOCATION OF ACCESSIBLE ENTRANCES - NOT ADDRESSED |
| | LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES - NOT |
| | ADDRESSED. SPACES SHOWN WITH NO ACCESS AISLES AND NEED |
| | 2 ADDITIONAL SPACES |
| | SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY - NOT ADDRESSED. |
| | ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE |
| | ENTRANCE - NOT ADDRESSED. |
| | |
| | SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2 |
| | (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE |
| | ROUTE). |
| | |
| | YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL, |
| | PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS |
| | RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE |
| | PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR |
| | ACCESSIBLE DESIGN." |
| | |
| | HTTP://WWW.ADA.GOV/RESTRIPE.HTM |
| | |
| | 2. FBC 2010 ACCESSIBILITY ADVISORY 502.3, WHERE THE |
| | ACCESSIBLE ROUTE MUST CROSS VEHICULAR TRAFFIC LANES, |
| | MARKED CROSSINGS ENHANCE PEDESTRIAN SAFETY; PLEASE |
| | INDICATE LOCATION ON PLAN. |
| | |
| | 3. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE |
| | THEIR PRINTED NAME AND SIGNATURE ON THE PLAN, FBC 107. |
| | - NOT ADDRESSED. |
| | |
| | 4. PROVIDE A VERIFIABLE COPY OF THE CONTRACT FOR THIS |
| | JOB FBC 109 - NOT ADDRESSED. |
| | |
| | |