| Plan Review Notes For Permit 13090082 |
| Permit Number |
13090082 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-01 16:18:04 | GROUNDING ELECTRODE TO TIE INTO EXISTING GROUNDING | | | EELCTRODE SYSTEM (SINGLE POINT GROUNDING) 250.50, | | | 250.52 | | | CONDUCTORS TO BE RATED BASED ON OVERCURRENT PROTECTION | | | 240.6, 301.15 | | | PROVIDE GROUNDING SYSTEM FOR TRANSFORMER TB | | | REVIEW CANNOT BE COMPLETED |
|