| 2013-09-17 14:58:17 | PERMIT # 13090052 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | A SEPERATE PERMIT IS REQUIRED FOR THE INSTALLATION OF |
| | STAIRS. STAIRS AND EGRESS COMPONENTS SHALL CONFORM TO |
| | THE LIFE SAFETY REQUIREMENTS OF CHAPTER 7 OF NFPA 101 |
| | FLORIDA 2007 EDITION. |
| | |
| | PLANS DO NOT INDICATE IF BUILDING IS SPRINKLERED. |
| | PLEASE PROVIDE THIS INFORMATION. COMMON PATH OF TRAVEL |
| | FOR NON-SPRINKLED BUILDINGS IS 50 FT. |
| | |
| | PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES, |
| | OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY |
| | LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC. |
| | |
| | MEZZANINE APPEARS TO EXCEED ONE-THIRD THE SIZE OF THE |
| | FIRST FLOOR. PLEASE INDICATE ACTUAL SQUARE FOOTAGE FOR |
| | EACH SPACE INCLUDING OFFICES, WAREHOUSE AREA, AND |
| | MEZZANINE STORAGE SPACE. |
| | |
| | IT APPEARS THAT MEZZANINE MAY HAVE BEEN INSTALLED |
| | WITHOUT PERMITS. THE CITY OF WEST PALM BEACH HAS NO |
| | RECORDS TO INDICATE THAT MEZZANINE WAS INSTALLED WITH |
| | THE REQUIRED PERMITS. PROPERTY APPRAISER RECORDS |
| | INDICATE BUILDING IS 4,000 SQ. FT., BUT DO NOT INCLUDE |
| | A MEZZANINE IN THEIR CALCULATIONS. |
| | |
| | PREVIOUS FIRE INSPECTION RECORDS INDICATE THAT |
| | WOOD-WORKING IS CONDUCTED IN THIS BUILDING. PER NFPA 1, |
| | WOOD-WORKING AREAS IN EXCESS OF 2,500 SQ. FT. REQUIRE |
| | AN AUTOMATIC FIRE PROTECTION SYSTEM. |
| | |
| | PERMITS PREVIOUSLY ISSUED FOR DUST COLLECTION ARE |
| | EXPIRED. |
| | |
| | |