| Plan Review Notes For Permit 13090032 |
| Permit Number |
13090032 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-04 08:00:40 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE CERTAINTEED SYSTEM ON PAGE 28 SPECIFIED FOR THE | | | FLAT ROOF HAS A MAXIMUM DESIGN PRESSURE OF -52.5 PSF. | | | THE STRUCTURE IS LOCATED IN AREA WITH 170 MPH VULT/132 | | | MPH VASD WIND SPEED AND THE EXPOSURE CATEGORY IS C. | | | THEREFORE, THE UPLIFT PRESSURES FOR ROOF ZONES 2 AND 3 | | | ARE MORE THAN THE DESIGN PRESSURE OF THE ROOF SYSTEM. | | | SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING IN THE PERIMETER | | | (ROOF ZONE 2) AND CORNER (ROOF ZONE 3) AREAS OF THE | | | FLAT ROOF. SEE LIMITATION #7 ON PAGE 32 OF THE NOA | | | WHICH ALLOWS ENHANCED FASTENING TO INCREASE THE UPLIFT | | | PRESSURES IN THESE AREAS. FBC R301.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|