| Date |
Text |
| 2013-09-17 10:33:59 | FBC 2010 ACCESSIBILITY CODE |
| | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. SHEET P0.1: ON THE SANITARY ISO. THE 2ND FLOOR SINK |
| | IS REQUIRED TO CONNECT DOWNSTREAM OF THE RESTROOM WET |
| | VENT FOR THE WATER CLOSET & LAV. |
| | 909.1 HORIZONTAL WET VENT PERMITTED. |
| | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE |
| | VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE |
| | CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND |
| | FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION |
| | OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM |
| | FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH |
| | DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT |
| | INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE |
| | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO |
| | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL |
| | WET VENT. |
| | |
| | 2. SHEET P0.1: ON THE SANITARY ISO. THE SOIL STACK FOR |
| | THE 2ND FLOOR FIXTURES IS RUN THROUGH THE 1ST FLOOR |
| | RESTROOM. |
| | 909.1 HORIZONTAL WET VENT PERMITTED. |
| | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE |
| | VENTED BY A HORIZONTAL WET VENT... |
| | |
| | 3. SHEET P0.1: THE EVEVATOR SUMP PUMP IS NOT PERMITTED |
| | TO BE DIRECTLY CONNECTED TO THE SANITARY SYSTEM. |
| | 301.6 PROHIBITED LOCATIONS. |
| | PLUMBING SYSTEMS SHALL NOT BE LOCATED IN AN ELEVATOR |
| | SHAFT OR IN AN ELEVATOR EQUIPMENT ROOM. |
| | |
| | EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE |
| | PERMITTED AT THE BASE OF THE SHAFT, PROVIDED THAT THEY |
| | ARE INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM AND |
| | COMPLY WITH SECTION 1003.4. |
| | |
| | 4. SHEET P0.1: THE EVEVATOR SUMP PUMP WILL REQUIRE AN |
| | APPROVED OIL ALARM SYSTEM. |
| | 1003.4 OIL SEPARATORS REQUIRED. |
| | AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES |
| | WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND |
| | IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE |
| | INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR |
| | FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING |
| | INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF |
| | DISPOSAL. |
| | |
| | EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN |
| | HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM |
| | IS INSTALLED. |
| | |
| | 5. SHEET P0.1: THE WATER PIPE ISO. SHOWS 1" WATER |
| | SERVICE. THE PLUMBING FIXTURE SCHEDULE CALLS FOR FLUSH |
| | VALVE TYPE WATER CLOSETS. FROM TABLE 603.1, 1 1/2" PIPE |
| | WOULD BE REQUIRED OR PLEASE PROVIDE CALCULATIONS. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |