Plan Review Notes
Plan Review Notes For Permit 13090031
Permit Number 13090031
Review Stop P
Sequence Number 1
Notes
Date Text
2013-09-17 10:33:59FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P0.1: ON THE SANITARY ISO. THE 2ND FLOOR SINK
 IS REQUIRED TO CONNECT DOWNSTREAM OF THE RESTROOM WET
 VENT FOR THE WATER CLOSET & LAV.
 909.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH
 DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 2. SHEET P0.1: ON THE SANITARY ISO. THE SOIL STACK FOR
 THE 2ND FLOOR FIXTURES IS RUN THROUGH THE 1ST FLOOR
 RESTROOM.
 909.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT...
  
 3. SHEET P0.1: THE EVEVATOR SUMP PUMP IS NOT PERMITTED
 TO BE DIRECTLY CONNECTED TO THE SANITARY SYSTEM.
 301.6 PROHIBITED LOCATIONS.
 PLUMBING SYSTEMS SHALL NOT BE LOCATED IN AN ELEVATOR
 SHAFT OR IN AN ELEVATOR EQUIPMENT ROOM.
  
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT, PROVIDED THAT THEY
 ARE INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM AND
 COMPLY WITH SECTION 1003.4.
  
 4. SHEET P0.1: THE EVEVATOR SUMP PUMP WILL REQUIRE AN
 APPROVED OIL ALARM SYSTEM.
 1003.4 OIL SEPARATORS REQUIRED.
 AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES
 WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND
 IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE
 INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR
 FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING
 INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF
 DISPOSAL.
  
 EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN
 HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM
 IS INSTALLED.
  
 5. SHEET P0.1: THE WATER PIPE ISO. SHOWS 1" WATER
 SERVICE. THE PLUMBING FIXTURE SCHEDULE CALLS FOR FLUSH
 VALVE TYPE WATER CLOSETS. FROM TABLE 603.1, 1 1/2" PIPE
 WOULD BE REQUIRED OR PLEASE PROVIDE CALCULATIONS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  