Plan Review Notes
Plan Review Notes For Permit 13090031
Permit Number 13090031
Review Stop M
Sequence Number 1
Notes
Date Text
2013-10-11 14:54:01PLANS DENIED
 1) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 (FOR FRESH AIR AND EXHAUST) 2010 FLORIDA ENERGY CODE.
 2) PROVIDE NOA FOR CONDENSER STAND.
 PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676