| Plan Review Notes For Permit 13090031 |
| Permit Number |
13090031 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-10-17 17:21:33 | THE FOLLOWING CORRECTIONS/ADJUSTMENTS NEED TO BE | | | ADDRESSED: | | | 1. TAKING INTO ACCOUNT THE ADJUSTMENT FACTORS OF NEC | | | 310.15(B)(2)(A) REQUIRED FOR FOUR CURRENT CARRYING | | | CONDUCTORS IN A RACEWAY AND THE VALUES AS PER NEC | | | 310.16, THIS FEEDER WILL ONLY WORK IF USING 90 DEGREE | | | INSULATION. | | | THE LESSER 75 DEGREE COLUMN LIMITS 500 MCM TO 380 AMP | | | AND APPLYING THE CORRECTION FACTORS OF 310.15 OF 80% | | | REDUCES THE AMPACITY OF THE CONDUCTOR TO ONLY 304 AMP. | | | | | | MAKE THE CORRESPONDING NOTES ON THE DRAWINGS |
|